CompoBus/D Communications Line Design

Chapter 2

 

 

 

3Compare the values found in steps 1 and 2, above. If the first value (A) is less than the second (B), this shows that power supply specifications are met and power can be supplied to all nodes at any point in the Network.

Note Be sure to refer to the correct graph as the maximum current flow is different for Thick and Thin Cables.

HCountermeasures

If the second value (B) is less than the first (A), use the following procedure to locate the communica- tions power supply.

Locate the communications power supply in the center of the Network and the nodes to both sides of it.

If the nodes are already located at both sides of the power supply, move the power supply in the direc- tion that requires the larger current capacity.

If Thin Cable is being used, replace it with Thick Cable.

Note If, after following the above procedure, B is still less than A, go to Step 2 and determine the actual position of the nodes by the formula calculation method.

DCalculation Example

The following example shows a Network that requires power to be supplied for 240 m on Thick Cable. The power supply is located in the center of the Network. Because the power supply is in the center, the maximum current will flow both to the left and to the right, enabling the supply of at least twice the maxi- mum current as when the power supply is placed on the end of the Network. The current consumption for individual nodes is as follows:

Terminating Resistor

Trunk line

 

 

 

Trunk line

Terminating Resistor

 

(5-wire cable)

 

 

 

(5-wire cable)

 

 

 

 

3 m max.

 

 

 

Node

Node

Node

Communications

Node

Node

Node

power supply

 

 

 

 

 

 

0.1 A

0.25 A

0.2 A

 

0.15 A

0.25 A

0.15 A

 

120 m

 

 

 

120 m

 

Trunk line

Power supply cable

Total power supply length on left = Total power supply length on right = 120 m Total current consumption on left: 0.1 + 0.25 + 0.2 = 0.55 A

Total current consumption on right: 0.15 + 0.25 + 0.15 = 0.55 A

Maximum current for the left side of the Thick Cable (see previous table) = approx. 2.5 A Maximum current for the right side of the Thick Cable (see previous table) = approx. 2.5 A (using straight line approximation between 100 to 150 m)

2-3-3 Step 2: Calculating the Best Location of the Actual Nodes