Omron 3G3FV-PDRT1-SIN Special Remote I/O, Inputs 3G3FV to Sysmac PC Instance ID 71 Dec 47 Hex

Models: 3G3FV-PDRT1-SIN

1 161
Download 161 pages 943 b
Page 69
Image 69

CompoBus/D Communications Card Operations

 

Chapter 5

D Inputs (3G3FV to SYSMAC PC)

 

 

Instance ID: 71 Dec (47 Hex)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Byte number

 

Bit 7

Bit 6

Bit 5

 

Bit 4

Bit 3

Bit 2

Bit 1

 

Bit 0

 

 

 

 

 

 

 

 

 

 

 

 

 

Wd m

Rightmost

0

At

Reference

Control

 

Inverter

During

During

Warning

 

Fault

 

 

 

Reference

From Net

From Net

 

Ready

reverse

forward

(minor

 

 

 

 

 

 

 

 

 

 

run

run

fault)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Leftmost

1

 

 

 

 

 

 

 

 

 

 

Wd m+1

Rightmost

2

Rotational speed monitor (rightmost data)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Leftmost

3

Rotational speed monitor (leftmost data)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note A shaded box indicate that the bit is not used.

HSpecial Remote I/O

Special remote I/O enables using all the functions of 3G3FV-series Inverters, and accessing/setting all parameters.

D Outputs (SYSMAC PC to 3G3FV)

 

Instance ID: 100 Dec (64 Hex)

 

Byte number

 

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

 

Bit 0

 

 

 

 

 

 

 

 

 

 

 

 

Wd n

Rightmost

0

Function code (write/read code)

 

 

 

 

 

 

 

 

 

 

 

 

Leftmost

1

Register number, leftmost byte (register number assigned to various parameters, etc.)

 

 

 

 

 

 

Wd n+1

Rightmost

2

Register number, rightmost byte (register number assigned to various parameters, etc.)

 

 

 

 

 

 

 

 

 

 

Leftmost

3

Register data, leftmost byte (data to write to specified register)

 

 

 

 

 

 

 

 

 

 

 

 

Wd n+2

Rightmost

4

Register data, rightmost byte (data to write to specified register)

 

 

 

 

D Inputs (3G3FV to SYSMAC PC)

 

 

Instance ID: 150 Dec (96 Hex)

 

Byte number

 

Bit 7

Bit 6

Bit 5

 

Bit 4

Bit 3

 

Bit 2

Bit 1

 

Bit 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wd m

Rightmost

0

Function code (returns transmitted code)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Leftmost

1

Register number, leftmost byte (returns transmitted register number)

 

 

 

 

 

 

 

 

 

 

 

 

Wd m+1

Rightmost

2

Register number, rightmost byte (returns transmitted register number)

 

 

 

 

 

 

 

 

 

 

 

 

 

Leftmost

3

Register data, leftmost byte (return transfer data amount or read data)

 

 

 

 

 

 

 

 

 

 

 

Wd m+2

Rightmost

4

Register data, rightmost byte (return transfer data amount or read data)

 

 

 

Note

1.

Special remote I/O outputs and inputs are paired. When using special remote I/O, be sure to

 

 

set them together.

Note

2.

Special remote I/O objects do not conform to the AC/DC drive profile, but are specially set for

 

 

this product.

Note

3.

The 16-bit data (register number and register data) is set using two words for each setting.

Note

4.

Be careful of the order of the leftmost and rightmost bytes of the 16-bit data. The order is re-

 

 

versed from that of basic and standard remote I/O.

Note

5.

For details on special remote I/O operation, refer to 5-4 Special Remote I/O.

5-7

Page 69
Image 69
Omron 3G3FV-PDRT1-SIN user manual Special Remote I/O, Inputs 3G3FV to Sysmac PC Instance ID 71 Dec 47 Hex