CompoBus/D Communications Card Operations | Chapter 5 | |
|
|
|
5-4-4 Inverter Monitoring Functions
All Inverter monitoring can be accessed. To read Inverter status, fault monitoring, alarm monitoring, I/O status monitoring, error log, etc., specify the register number from the following table and read the data.
Register number (hex) | Function | Content | Read | Write |
|
|
|
|
|
0010 | Inverter status | (Refer to table below.) | Yes | No |
|
|
|
|
|
0011 | Operator status | (Refer to table below.) | Yes | No |
|
|
|
|
|
0012 | Operator setting error | OPE error number | Yes | No |
| number |
|
|
|
0013 | Not used. |
|
|
|
|
|
|
|
|
0014 | Fault 1 | (Refer to table below.) | Yes | No |
|
|
|
|
|
0015 | Fault 2 | (Refer to table below.) | Yes | No |
|
|
|
|
|
0016 | Fault 3 | Not used. | Yes | No |
|
|
|
|
|
0017 | CPF error 1 | (Refer to table below.) | Yes | No |
|
|
|
|
|
0018 | CPF error 2 | (Refer to table below.) | Yes | No |
|
|
|
|
|
0019 | Alarm 1 | (Refer to table below.) | Yes | No |
|
|
|
|
|
001A | Alarm 2 | (Refer to table below.) | Yes | No |
|
|
|
|
|
001B to 001F | Not used. | (Refer to table below.) |
|
|
DInverter Status: Register Number 0010 Hex
Bit | Content |
|
|
0 | During RUN |
|
|
1 | Zero speed |
|
|
2 | Forward/reverse (1: Reverse operation) |
|
|
3 | During Fault Reset input |
|
|
4 | Frequency agree 1 |
|
|
5 | Inverter operation ready |
|
|
6 | Alarm |
|
|
7 | Fault |
|
|
8 to 15 | Not used. |
DOperator Status: Register Number 0011 Hex
Bit | Content | |
|
| |
0 | 1: Operation fault | |
|
| |
1 | 1: EEPROM error | |
|
| |
2 | 1: Program mode | |
|
| |
3 | 00: Operator connecting | |
| 11: Operator disconnecting | |
4 | ||
| ||
|
| |
5 to 15 | Not used. |