Omron 3G3FV-PDRT1-SIN user manual Chapter

Models: 3G3FV-PDRT1-SIN

1 161
Download 161 pages 943 b
Page 152
Image 152

Appendices

 

 

 

 

 

Chapter 8

 

 

 

 

 

 

 

 

 

 

Instance

Attribute

Name

Content

Setting

Default

Read

Write

Size

 

 

 

 

range

(Hex)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

09

Expected packet rate

Indicates the length of the

0 to

09C4

Yes

Yes

Word

Explicit

 

 

internal processing timeout

65,535

(2,500

 

 

 

 

message

 

 

when a communications

(ms)

ms)

 

 

 

 

 

 

 

request is received.

 

 

 

 

 

 

 

 

 

Incremented by 10-ms

 

 

 

 

 

 

 

 

 

units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0C

Watchdog time-out

Indicates the action for

---

01

Yes

No

Byte

 

 

action

internal processing timeout

 

 

 

 

 

 

 

 

 

related to communications.

 

 

 

 

 

 

 

 

 

00: Retain timeout status

 

 

 

 

 

 

 

 

 

(until reset or cleared).

 

 

 

 

 

 

 

 

 

01: Cut connection

 

 

 

 

 

 

 

 

 

automatically.

 

 

 

 

 

 

 

 

 

02: Operate again with

 

 

 

 

 

 

 

 

 

same connection as is.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0D

Produced connection

Indicates number of bytes

---

0000

Yes

No

Word

 

 

path length

of data for produced

 

 

 

 

 

 

 

 

 

connection path. (No data

 

 

 

 

 

 

 

 

 

for explicit messages.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0E

Produced connection

Indicates the data for

---

---

Yes

No

Array

 

 

path

defining the application

 

 

 

 

 

 

 

 

 

object for sending this

 

 

 

 

 

 

 

 

 

object (instance). (No data

 

 

 

 

 

 

 

 

 

for explicit messages.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0F

Consumed connection

Indicates the number of

---

0000

Yes

No

Word

 

 

path length

bytes of data for the

 

 

 

 

 

 

 

 

 

consumed connection path.

 

 

 

 

 

 

 

 

 

(No data for explicit

 

 

 

 

 

 

 

 

 

messages.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Consumed connection

Indicates the data for

---

---

Yes

No

Array

 

 

path

defining the application

 

 

 

 

 

 

 

 

 

object for receiving this

 

 

 

 

 

 

 

 

 

object (instance). (No data

 

 

 

 

 

 

 

 

 

for explicit messages.)

 

 

 

 

 

 

8-8

Page 152
Image 152