Communications Programs (SYSMAC C200HX/HG/HE PCs)

Chapter 7

 

 

 

HTiming Chart

00000 (Write Parameter Input Bit)

03000 (Data Write Flag)

03005 (Data Agree Flag)

00100 (Sending Written Data Flag)

00101 (Sending Enter Command Flag)

00102 (Sending “00” Function Flag)

00103 (Data Write Completed Flag)

Word n to n+2 (Send Data)

Word m to m+2 (Receive Data)

Send Data (Write) Enter Command

“00” Function

Send Data (Write)

Enter Command “00” Function

1.2.3.4.

HOperation

1.Set the register number of the parameter and the data to be written in DM 0000 and DM 0001 re- spectively. When the Write Parameter Input Bit is turned ON, the Data Write Flag will be turned ON and parameter writing processing will be executed.

2.If the data is properly written, the written parameter register number and the function code will be returned from the Inverter. When the sent register number and the function code agree with the re- ceived data contents, the Data Agree Flag will be turned ON to send the enter command.

3.If the enter command is normally received, the register number and function code that agree with the enter command will be returned from the Inverter. When the sent register number and function code agree with the received contents, the Data Agree Flag will be turned ON to send the function code “00” (both the register number and function code are 0000).

4.In the same manner, if the function code “00” is normally received, the Data Agree Flag will be turned ON and the Data Write Completed Flag will be turned ON. When the Data Write Completed Flag turns ON, the Data Write Flag will turn OFF and the program will stop.

Note

1.

If the enter command remains set, data will be repeatedly written to EEPROM. Therefore, set

 

 

the function code to “00” (both the register number and function code are 0000), which per-

 

 

forms no processing, to disable the enter command.

Note

2.

If the sent data is faulty, word m bit 7 will be turned ON, which will turn ON the Faulty Data Flag

 

 

and the program will be stopped until the Faulty Data Reset Input Bit (00002) is turned ON.

7-23