Chapter 7

 

 

 

HTiming Chart

00000

(Frequency Reference Input Bit)

00001

(Forward Input Bit)

00002

(Reverse Input Bit)

Word m bit 2

(During Forward Run)

Word m bit 3

(During Reverse Run)

Rotational speed reference data

03000 (Fault Flag)

00003 (Fault Reset Input Bit)

DM 0000 (rotational speed reference data transmitted to words n + 1)

1.

2.

3.

4.

5.

6.

7.

HOperation

1.When the Frequency Reference Input Bit turns ON, the rotational speed reference data specified in DM 0000 is moved to remote I/O output word n + 1.

2.When the Forward Input Bit turns ON, remote I/O word n bit 0 (Forward/Stop) will turn ON, and for- ward operation will start. During forward operation, remote I/O word m bit 2 (During Forward Run) will be ON.

3.When the Forward Input Bit turns OFF, remote I/O word m bit 2 (During Forward Run) will turn OFF after operation will decelerate to a stop.

4.When the Reverse Input Bit turns ON, remote I/O word n bit 1 (Reverse/Stop) will turn ON, and re- verse operation will start. During reverse operation, remote I/O word m bit 3 (During Reverse Run) will be ON.

5.When the Reverse Input Bit turns OFF, remote I/O word m bit 3 (During Reverse Run) will turn OFF after operation decelerates to a stop.

6.When the remote I/O Fault Bit (word m bit 0) turns ON, the Fault Flag will turn ON.

7.When the Fault Reset Input Bit turns ON, remote I/O word n bit 2 (Fault Reset Input Bit) will turn ON, and the fault will be cleared. When the fault is reset, the Fault Flag will turn OFF simultaneously.