Omron 3G3FV-PDRT1-SIN user manual Basic Concept

Models: 3G3FV-PDRT1-SIN

1 161
Download 161 pages 943 b
Page 24
Image 24

CompoBus/D Communications Line Design

Chapter 2

 

 

 

2-3 Communications Power Supply

2-3-1 Locating the Communications Power Supply

HBasic Concept

The communications power supply must be 24 VDC.

Make sure that the power is supplied from the trunk line.

When providing power to several nodes from one power supply, if possible try to locate the nodes in both directions from the power supply.

Provide power through Power Supply Taps. It is, however, possible to use T-branch Taps instead when there is one communications power supply in the system and the total current consumption is less than 5 A.

The power supply capacity for cables is restricted to 8 A for Thick Cables and 3 A for Thin Cables.

A single Network is usually supplied by one power supply. It is, however, possible to have more than one power supply when power supply specifications cannot be met with a single power supply. (See 2-3-4 Step 3: Splitting the System into Multiple Power Supplies.)

Fully consider the power supply capacity allowance in the design.

If the power supply is switched OFF during the operation of the Network, there may be a malfunction in the nodes.

The current capacity of the drop line varies according to its length. The longer the drop line, the lower its maximum capacity becomes. This is the same whether the cable is thick or thin. Calculate the cur- rent capacity passing through the drop line I (the total current consumption at the drop line) using the following formula.

I = 4.57/L

I:

Permissible current (A)

 

L:

Length of the drop line (m)

2-6

Page 24
Image 24
Omron 3G3FV-PDRT1-SIN user manual Basic Concept