CompoBus/D Communications Card Operations

Chapter 5

 

 

 

HObject Details

Instance

Attribute

Name

Content

Setting

Default

 

Read

Write

Size

 

 

 

 

 

range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

 

01

Object Software

Indicates class 29 software

---

0001

 

Yes

No

Word

 

 

 

Revision

revisions. The revision value is

 

 

 

 

 

 

 

 

 

 

advanced whenever there is a

 

 

 

 

 

 

 

 

 

 

change.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

 

03

Forward/Stop

00: Stop

00, 01

00

 

Yes

Yes

Byte

 

 

 

 

01: Forward operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

Reverse/Stop

00: Stop

00, 01

00

 

Yes

Yes

Byte

 

 

 

 

01: Reverse operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

Net Control

00: Operate by b1–02 setting.

00, 01

00

 

Yes

Yes

Byte

 

 

 

Local/remote switch

01: Operate by CompoBus/D with

 

 

 

 

 

 

 

 

 

Set note 1.

b1–02 set to “3.”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

State

03 hex: Inverter ready

---

03

 

Yes

No

Byte

 

 

 

Inverter status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07

During forward run

00: No Inverter output or operating

---

00

 

Yes

No

Byte

 

 

 

 

in reverse.

 

 

 

 

 

 

 

 

 

 

01: Forward operation or DC

 

 

 

 

 

 

 

 

 

 

braking

 

 

 

 

 

 

 

 

 

 

Turns ON even for DC braking

 

 

 

 

 

 

 

 

 

 

during reverse operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08

During reverse run

00: No Inverter output or operating

---

00

 

Yes

No

Byte

 

 

 

 

in forward.

 

 

 

 

 

 

 

 

 

 

01: Operating in reverse (reverse

 

 

 

 

 

 

 

 

 

 

operation output status)

 

 

 

 

 

 

 

 

 

 

Becomes “00” with DC braking.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09

Inverter Ready

00: Preparing

---

00

 

Yes

No

Byte

 

 

 

 

Initial processing/ not drive mode/

 

 

 

 

 

 

 

 

 

 

fault

 

 

 

 

 

 

 

 

 

 

01: Inverter ready

 

 

 

 

 

 

 

 

 

 

Inverter can receive run

 

 

 

 

 

 

 

 

 

 

command.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0A

Fault

00: Normal

---

00

 

Yes

No

Byte

 

 

 

 

01: Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0B

Warning (minor fault)

00: Normal

---

00

 

Yes

No

Byte

 

 

 

 

01: Warning (minor fault)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0C

Fault Reset

00: Normal status

00, 01

00

 

Yes

Yes

Byte

 

 

 

 

01: Fault reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0D

Fault code

Indicates the contents of fault that

---

0000

 

Yes

No

Word

 

 

 

 

occur. (See the fault code list on

 

 

 

 

 

 

 

 

 

 

the following page.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0F

Control From Net

00: Operating by b1–02 setting.

---

00

 

Yes

No

Byte

 

 

 

Run signal input

01: Operating by CompoBus/D.

 

 

 

 

 

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

See note 1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

DeviceNet Fault

02: Maker’s specifications

---

02

 

Yes

No

Byte

 

 

 

mode

 

 

 

 

 

 

 

 

 

 

See note 2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Force Fault/Trip

00: Normal operation

00, 01

00

 

Yes

Yes

Byte

 

 

 

Communications

01: Communications external fault

 

 

 

 

 

 

 

 

 

input (according to parameter F9 )

 

 

 

 

 

 

 

 

 

external fault input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Force Status

00: Normal status

---

00

 

Yes

No

Byte

 

 

 

Communications

01: Communications external fault

 

 

 

 

 

 

 

 

 

detected. (Inverter stopped with

 

 

 

 

 

 

 

 

 

external fault input

 

 

 

 

 

 

 

 

 

fault detection.)

 

 

 

 

 

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note

1. The Net Control and Control From Net functions are applicable for Inverter software versions

 

 

S1042 and later. Cannot be changed during running. Check the version with the Inverter mon-

 

 

itor function U1–14. If the software version is S1040, set b1–02 to “3.”

 

 

 

5-18