Channels

Temperature

Temperature input channels monitor RTD or thermocouple temperature sensors inputs for the most common ranges. You can also configure severity alarms that can send an email, a syslog message, and/or an SNMP trap when an alarm is triggered or cleared; See Alarm Settings on page 271 for more information about the alarms.

RTD ranges are:

z Pt100 a=385 -50 to 150C

z Pt100 a=392 -50 to 150C

z Pt1000 a=385 -40 to 160C

 

 

 

 

z Pt100 a=385 0 to 100C

z Pt100 a=392 0 to 100C

z

NiFe604 a=518 -80 to 100C

 

 

 

 

z Pt100 a=385 0 to 200C

z Pt100 a=392 0 to 200C

z

NiFe604 a=518 0 to 100C

 

 

 

 

 

 

 

 

z

Pt100 a=385

0 to 400C

z

Pt100 a=392

0 to 400C

 

 

 

 

 

 

 

 

 

 

z

Pt100 a=385

-200 to 200C

z

Pt100 a=392

-200 to 200C

 

 

 

 

 

 

 

 

 

 

Note: IEC RTD 100 ohms.=0.00385

JIS RTD 100 ohms.=0.00392

Thermocouple ranges are:

z B 500 to 1800C

z K 0 to 1370C

z T -100 to 400C

 

 

 

 

 

z

E 0 to 1000C

z

R 500 to 1750C

 

 

 

 

 

 

z

J 0 to 760C

z

S 500 to 1750C

 

 

 

 

 

 

In the following example, a Temperature I/O IOLAN is used to monitor industrial freezer temperature sensors, with an alarm set to send a syslog message if the temperature rises above 31o C.