Trigger

If the Trigger Type is Low, an alarm is triggered when the input drops below

 

the specified Trigger value; other severity level trigger values must decrease in

 

value with each subsequent level. If the Trigger Type is High, an alarm is

 

triggered when the input is higher than the specified Trigger value; other

 

severity level trigger values must increase in value with each subsequent level.

Clear

To clear an alarm, the input must drop below the specified value when Trigger

 

Type is High or go above the specified value when Trigger Type is Low.

Email

When enabled, sends an email alert to an email account(s) set up in the System

 

settings when an alarm is triggered or cleared. The email alert data includes the

 

severity level and the value that caused the alarm to trigger or clear. The Email

 

Alert is associated with Level Critical.

 

Default: Disabled

Syslog

When enabled, sends a message to syslog when an alarm is triggered or

 

cleared. The syslog entry includes the severity level and the value that caused

 

the alarm to trigger or clear. The syslog message is associated with Level

 

Critical.

 

Default: Disabled

SNMP

When enabled, sends an SNMP trap when an alarm is triggered or cleared. The

 

trap consists of the severity level and whether the alarm was triggered or

 

cleared.

 

Default: Disabled