Request Queuing When enabled, allows multiple, simultaneous messages to be queued and
processed in order of reception.
Default: Enabled
Embedded When this option is selected, the address of the slave Modbus devi ce is
embedded in the message header.
Default: Enabled
Remapped Used for single device/port operation. Older Modbus devices may not include a
UID in their transmission header. When this option is selected, you can specify
the UID that will be inserted into the message header for the Modbus slave
device. This feature supersedes the Broadcast feature.
Default: Disabled
Remap UID Specify the UID that will be inserted into the message head er for the Sl ave
Modbus serial de vice.
Range: 1-247
Default: 1
Enable SSL/TLS
using global settings When enabled, Modbus Slave Gateway messages to remote TCP Modbus
Masters are encrypted via SSL/TLS.
Default: Disabled