Set IOChannel
Set IOChannel Analog (Temperature)
Description Sets the Analog input channel settings for Temperature models.
User Level Admin
Syntax set iochannel <analog_channel> type rtdthermocouple range <range_specifier>
set iochannel <analog_channel> alarm
[level 12345 [mode onoff]
Options analog_channel
Specify the Analog channel number, for example, a2 or a4 (this also applies to
Temperature models).
type
Specify the type of sensor you are using to measure temperature, either RTD or thermocouple. The default is RTD.
range
Specify the temperature range that you want to measure. For RTD, the range is:
z1 (Pt100 a=385
z2 (Pt100 a=385 0 to 100C)
z3 (Pt100 a=385 0 to 200C)
z4 (Pt100 a=385 0 to 400C)
z5 (Pt100 a=385
z6 (Pt100 a=392
z7 (Pt100 a=392 0 to 100C)
z8 (Pt100 a=392 0 to 200C)
z9 (Pt100 a=392 0 to 400C)
z10 (Pt100 a=392
z11 (Pt1000 a=385
z12 (NiFe604 a=518
z13 (NiFe604 a=518 0 to 100C)
For thermocouple, the range is:
zb (B 500 to 1800C)
ze (E 0 to 1000C)
zj (J 0 to 760C) This is the default.
zk (K 0 to 1370C)
zr (R 500 to 1750C)
zs (S 500 to 1750C)
zt (T
alarm
Configures alarm settings when the Analog input trigger is activated.
86 | IOLAN DS1/TS2 CLI Reference Guide, Version 4.1 |