Set IOChannel

Set IOChannel Analog (Temperature)

Description Sets the Analog input channel settings for Temperature models.

User Level Admin

Syntax set iochannel <analog_channel> type rtdthermocouple range <range_specifier>

set iochannel <analog_channel> alarm

[level 12345 [mode onoff] [trigger-type disabledlowhigh] [trigger-level <decimal_value>] [clear-mode automanual] [clear-level <decimal_value>] [snmp onoff] [syslog onoff]]

Options analog_channel

Specify the Analog channel number, for example, a2 or a4 (this also applies to

Temperature models).

type

Specify the type of sensor you are using to measure temperature, either RTD or thermocouple. The default is RTD.

range

Specify the temperature range that you want to measure. For RTD, the range is:

z1 (Pt100 a=385 -50 to 150C) This is the default.

z2 (Pt100 a=385 0 to 100C)

z3 (Pt100 a=385 0 to 200C)

z4 (Pt100 a=385 0 to 400C)

z5 (Pt100 a=385 -200 to 200C)

z6 (Pt100 a=392 -50 to 150C)

z7 (Pt100 a=392 0 to 100C)

z8 (Pt100 a=392 0 to 200C)

z9 (Pt100 a=392 0 to 400C)

z10 (Pt100 a=392 -200 to 200C)

z11 (Pt1000 a=385 -40 to 160C)

z12 (NiFe604 a=518 -80 to 100C)

z13 (NiFe604 a=518 0 to 100C)

For thermocouple, the range is:

zb (B 500 to 1800C)

ze (E 0 to 1000C)

zj (J 0 to 760C) This is the default.

zk (K 0 to 1370C)

zr (R 500 to 1750C)

zs (S 500 to 1750C)

zt (T -100 to 400C).

alarm

Configures alarm settings when the Analog input trigger is activated.

86

IOLAN DS1/TS2 CLI Reference Guide, Version 4.1