Set Line
Set IO Failsafe
Description | Sets the failsafe (watchdog) settings for I/O. |
User Level | Admin |
Syntax | set io failsafe [mode onoff] [timeout <seconds>] |
Options | mode |
| Enables/disables the Failsafe Timer. This is the global setting that must be enabled to |
| set the Failsafe Action on the channel for digital outputs and relays. When this timer |
| expires because of no I/O activity within the specified time interval, the Failsafe Action |
| set for the channel determines the action on the output. |
| timeout |
| The number of seconds that must elapse with no I/O activity before the channel |
| Failsafe Action is triggered. Valid values are |
Set IO Modbus
Description | Enabling the Modbus option makes the IOLAN act as a Modbus Slave, allowing |
User Level | Modbus Masters to communicate with the IOLAN to control and/or retrieve I/O data. |
Admin | |
Syntax | set io modbus [mode onoff] [uid |
Options | mode |
| Enables/disables the ability to control/monitor I/O channels using the Modbus protocol. |
| uid |
| This is the UID you are assigning to the IOLAN, which is acting as a Modbus slave. |
Set IO Temperature-Scale
Description | Sets the temperature scale that will be used for all Temperature input readings. |
User Level | Admin |
Syntax | set io |
Option | |
| Select the temperature scale that will be used to display temperature data, either |
| Fahrenheit or Celsius. The default is Celsius. |
Set Line
Set Line Service
Description Sets the Line Service settings to signal I/O. When the line service is set to
User Level Admin
Syntax set line <number> service
Option signal-io
Sets the line to use signal I/O. You still need to define the serial pins for digital input (CTS, DSR, or DCD) or digital output (RTS or DTR). See Set IOChannel Digital Input (Serial Pins) on page 80 or Set IOChannel Digital Output (Serial Pins) on page 83 for configuration options.