Settings

Request Queuing

When enabled, allows multiple, simultaneous messages to be queued and

 

processed in order of reception.

 

Default: Enabled

Embedded

When this option is selected, the address of the slave Modbus device is

 

embedded in the message header.

 

Default: Enabled

Remapped

Used for single device/port operation. Older Modbus devices may not include a

 

UID in their transmission header. When this option is selected, you can specify

 

the UID that will be inserted into the message header for the Modbus slave

 

device. This feature supersedes the Broadcast feature.

 

Default: Disabled

Remap UID

Specify the UID that will be inserted into the message header for the Slave

 

Modbus serial device.

 

Range: 1-247

 

Default: 1

Enable SSL/TLS When enabled, Modbus Slave Gateway messages to remote TCP Modbus using global settings Masters are encrypted via SSL/TLS.

Default: Disabled

238

IOLAN SDS/SCS/STS User’s Guide, Version 3.6

Page 238
Image 238
Perle Systems STS, SCS manual Request Queuing, Default Enabled