Modbus I/O Access

A4D2/A4R2 Registers

The following coils and registers are supported by the IOLAN A4D2 and A4R2 I/O models:

 

Data Model

A1

A2

A3

A4

D1/R1

D2/R2

R/W

 

 

 

 

 

 

 

 

 

Coils:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MB_REG_DI_SENSOR

-----

-----

-----

-----

6149

6150

R

 

 

 

 

 

 

 

 

 

*

MB_REG_DI_SENSOR_ALARM_STATE

-----

-----

-----

-----

6213

6214

R/W

 

 

 

 

 

 

 

 

 

 

MB_REG_DO_SENSOR

-----

-----

-----

-----

6661

6662

R/W

 

 

 

 

 

 

 

 

 

Holding Registers:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MB_REG_HR_DI_SENSOR_LATCH

-----

-----

-----

-----

6149

6150

R/W

 

 

 

 

 

 

 

 

 

 

MB_REG_HR_DO_SENSOR_PULSE_ISW

-----

-----

-----

-----

6213

6214

R/W

 

 

 

 

 

 

 

 

 

 

MB_REG_HR_DO_SENSOR_PULSE_ASW

-----

-----

-----

-----

6277

6278

R/W

 

 

 

 

 

 

 

 

 

 

MB_REG_HR_DO_SENSOR_PULSE_COUNT

-----

-----

-----

-----

6341

6342

R/W

 

 

 

 

 

 

 

 

 

 

MB_REG_HR_AI_CLEAR_ALARM_LATCH

2049

2050

2051

2052

-----

-----

W

 

 

 

 

 

 

 

 

 

 

MB_REG_HR_AI_CLEAR_MAX

2113

2114

2115

2116

-----

-----

W

 

 

 

 

 

 

 

 

 

 

MB_REG_HR_AI_CLEAR_MIN

2177

2178

2179

2180

-----

-----

W

 

 

 

 

 

 

 

 

 

Input Registers:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MB_REG_IR_CURR_ENG

2080

2112

2144

2176

-----

-----

R

 

 

 

 

 

 

 

 

 

 

MB_REG_IR_MIN_ENG

2082

2114

2146

2178

-----

-----

R

 

 

 

 

 

 

 

 

 

 

MB_REG_IR_MAX_ENG

2084

2116

2148

2180

-----

-----

R

 

 

 

 

 

 

 

 

 

 

MB_REG_IR_CURR_RAW

2086

2118

2150

2182

-----

-----

R

 

 

 

 

 

 

 

 

 

 

MB_REG_IR_MIN_RAW

2087

2119

2151

2183

-----

-----

R

 

 

 

 

 

 

 

 

 

 

MB_REG_IR_MAX_RAW

2088

2120

2152

2184

-----

-----

R

 

 

 

 

 

 

 

 

 

 

MB_REG_IR_ALARM_LEVEL

2089

2121

2153

2185

-----

-----

R

 

 

 

 

 

 

 

 

 

*For DI alarm state, read will get state, write will clear alarm.

271

Page 271
Image 271
Perle Systems SCS, STS manual A4D2/A4R2 Registers, Data Model D1/R1 D2/R2 Coils