Channels

Active Signal

How long the channel will be active during the pulse mode.

Width

Range: 1-9999 x 100 ms

 

Default: 1 (100 ms)

Delay

How long to delay an active-to-inactive or inactive-to-active setting after it is

 

manually started.

 

Range: 1-9999 x 100 ms

 

Default: 1 (100 ms)

Failsafe Action

When there has been no I/O activity within the specified time (set in the I/O

 

Interfaces, Settings on the Failsafe Timer tab) and the Failsafe Timer is

 

triggered.

 

Data Options:

 

z None—The state of the Digital/Relay output remains the same, no change.

 

z Activate Output—Activates the channel.

 

z Deactivate Output—Deactivates the channel.

 

Default: None

Digital I/O Extension

Overview

The Digital I/O extension feature connects a digital input signal to digital output(s)/relay(s) and/or a TCP/IP application over an IP network. Therefore, when the state of the digital input changes, you can also change the state of the digital output or relay channel or output serial signal pin on a local I/O channel(s), other IOLAN I/O channels, other IOLAN serial signal pins, or the data can be sent to an application(s).

For example, when the door opens (I/O digital input sensor) in a factory, a light goes on in the reception office (remote IOLAN relay channel), and the door open/close is logged by an application on a remote host.

Front Door

perle

IOLAN

Warehouse

perle IOLAN Reception

Network

Remote Host

253

Page 253
Image 253
Perle Systems SCS, STS manual Digital I/O Extension, Active Signal, Front Door, Warehouse Perle Iolan Reception