Configuring Modbus

Modbus Serial Port Settings

Modbus Master Settings

When the Modbus Masters is attached to the IOLAN’s serial port, configure that serial port to the Modbus Gateway profile acting as a Modbus Master. You must configure the Modbus TCP Slaves on the TCP/Ethernet side so the IOLAN can properly route messages, using the Modbus Slave’s UIDs, to the appropriate TCP-attached devices.

Modbus Slave

IP: 10.10.10.12

UID: 23

 

TCP

 

 

Master Gateway

Serial

EIA-232

 

Network

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IOLAN

EIA-422/485

Modbus Master

 

 

 

 

IP: 10.10.10.10

 

 

 

 

 

 

 

Modbus Slave

 

 

 

 

Serial Port 1

 

 

 

 

 

 

 

 

IP: 10.10.10.11

 

 

 

 

 

 

 

 

 

 

 

 

 

UID: 22

 

 

Modbus Master

 

 

 

 

 

 

 

 

To configure the Modbus Master on serial port 1, do the following:

1.Select the Modbus Gateway profile for serial port 1.

2.On the General tab, enable the Modbus Master parameter.

3.Click the Destination Slave IP Mappings button and click the Add button in the Destination Slave IP Mappings window.

4.Configure the Destination Slave IP Mappings window as follows:

The IOLAN will send a request and expect a response from the Modbus Slave with an IP

Address of 10.10.10.11 on Port 502 with UID 22 and from the Modbus Slave with and IP

Address of 10.10.10.12 on Port 502 with UID 23 (remember when Type is set to Host, the

IOLAN increments the last octet of the IP address for each UID specified in the range).