Channels
262 IOLAN SDS/SCS/STS User’s Guide, Version 3.6

Advanced Analog Alarm Settings

The advanced Analog Alarm Setting s window expands the basic alarm settings options to up to five
severity levels.
Configure the following parame ters:
Send Syslog Alert When enabled, sends a message to syslog when an alarm is triggered or
cleared. The syslog entry includes the severity level and the value that caused
the alarm to trigger or clear. The syslog message is associated with Level
Critical.
Default: Disabled
Send SNMP Alert When enabled, sends an SNMP trap when an alarm is triggered or cleared. The
trap consists of the severity level and whether the alarm was triggered or
cleared.
Default: Disabled
Trigger Type If the Trigger Type is Low, an alarm is triggered when the input drops below
the specified Trigger value; other severity level trigger values must decrease in
value with each subsequent level. If the Trigger Type is High, an alarm is
triggered when the input is higher than the specified Trigger value; other
severity level trigger values must increase in value with each subsequent level.
Clear Mode To clear an alarm, the input must drop below the specified value when Trigger
Type is High or go above the specified value when Trigger Type is Low.
Level 1-5 Defines the Level severity settings for up to five lev el s . If the Trigger Type is
Low, an alarm is triggered whe n th e input drops below the specified Trigger
value; other severity level trigger values must decrease in value with each
subsequent level. If the Trigger Type is High, an alarm is triggered when the
input is higher than the specified Trigger value; other severity level trigger
values must increase in value with each subsequent level.