Channels

Send Syslog Alert When enabled, sends a message to syslog when an alarm is triggered or cleared. The syslog entry includes the severity level and the value that caused the alarm to trigger or clear. The syslog message is associated with Level Critical.

Default: Disabled

Send SNMP Alert When enabled, sends an SNMP trap when an alarm is triggered or cleared. The trap consists of the severity level and whether the alarm was triggered or cleared.

Default: Disabled

Advanced Analog Alarm Settings

The advanced Analog Alarm Settings window expands the basic alarm settings options to up to five severity levels.

Configure the following parameters:

Trigger Type

If the Trigger Type is Low, an alarm is triggered when the input drops below

 

the specified Trigger value; other severity level trigger values must decrease in

 

value with each subsequent level. If the Trigger Type is High, an alarm is

 

triggered when the input is higher than the specified Trigger value; other

 

severity level trigger values must increase in value with each subsequent level.

Clear Mode

To clear an alarm, the input must drop below the specified value when Trigger

 

Type is High or go above the specified value when Trigger Type is Low.

Level 1-5

Defines the Level severity settings for up to five levels. If the Trigger Type is

 

Low, an alarm is triggered when the input drops below the specified Trigger

 

value; other severity level trigger values must decrease in value with each

 

subsequent level. If the Trigger Type is High, an alarm is triggered when the

 

input is higher than the specified Trigger value; other severity level trigger

 

values must increase in value with each subsequent level.

262

IOLAN SDS/SCS/STS User’s Guide, Version 3.6

Page 262
Image 262
Perle Systems STS, SCS manual Advanced Analog Alarm Settings, Trigger Type, Clear Mode