Appendix E MODBUS Commands

Series 24-HP Instruction Manual

gramming Output Menu’s “Modbus Units” item. The display units strings may be examined by accessing their associated registers. Each of these units string registers contain 2 characters of the string, and the strings may be 2 to 12 characters in length with unused characters set to zero. Note that the byte order affects the order in which the strings are transmitted. If the Modbus Order menu (see page 2) is set to 0-1:2-3 or 2-3:0-1, then the charac- ters are transmitted in the correct order; if set to 1-0:3-2 or 3-2:1- 0, then each pair of characters will be transmitted in reverse or- der.

Registers

Variable

Data type

Units

Function

Addresses

 

 

 

 

code

 

 

 

 

 

 

 

65100-65101

Serial number

unsigned long

03, 04

 

 

 

 

 

 

 

30525-30526

Totalizer

unsigned long

display units*

03, 04

524-525

32037-32042

Totalizer units

string

03, 04

2036-2041

30009-30010

Mass flow

float

display units*

03, 04

8-9

 

 

 

 

 

 

30007-30008

Volume flow

float

display units*

03, 04

6-7

 

 

 

 

 

 

30005-30006

Pressure

float

display units*

03, 04

4-5

 

 

 

 

 

 

30001-30002

Temperature

float

display units*

03, 04

0-1

 

 

 

 

 

 

30029-30030

Velocity

float

ft/sec

03, 04

28-29

 

 

 

 

 

 

30015-30016

Density

float

display units*

03, 04

14-15

 

 

 

 

 

 

30013-30014

Viscosity

float

cP

03, 04

12-13

30031-30032

Reynolds number

float

03, 04

30-31

30025-30026

Vortex frequency

float

Hz

03, 04

24-25

 

 

 

 

 

 

34532

Gain

char

03, 04

4531

30085-30086

Vortex amplitude

float

Vrms

03, 04

84-85

30027-30028

Filter setting

float

Hz

03, 04

26-27

 

 

 

 

 

 

The following registers are available with the energy meter firm-

ware:

Registers

30527-30528

32043-32048

30003-30004

30011-30012

Variable

Totalizer #2 Totalizer #2 units Temperature #2 Energy flow

Data type

unsigned long string

float float

Units

display units*

display units* display units*

Function code

03, 04 03, 04 03, 04 03, 04

Addresses

526-527

2042-2047

2-3

10-11

E-4

IM-24-HP

Page 86
Image 86
Sierra 241-VTP, 240-VTP instruction manual Appendix E Modbus Commands