Timed Relay Closing (Timer #1 - Day of Week)
Cmd Loc | 067 |
Default | 0 |
Range | 0 - 127 |
Timed Relay Closing (Timer #1 - Hours)
Cmd Loc | 068 |
Default | 0 |
Range | 0 - 23 |
Timed Relay Closing (Timer #1 - Minutes)
Cmd Loc 069
Default 0
Range 0 - 59
Block 7 - Auxiliary Devices Programming (cont.)
Comments | Options: (CL 067) | |
These Options will determine the Day(s) of | 0 | Disabled |
the Week and Time of Day when the pro- | 1 | Saturday |
grammed relay will automatically close. The | 2 | Friday |
value programmed into CL 067 is the total for | 4 | Thursday |
all days the relay is to be activated. The relay | 8 | Wednesday |
to be closed is programmed in Block 7, CL | 16 | Tuesday |
001 - 011 using Option 79. | 32 | Monday |
Once activated, the relay will remain closed | 64 | Sunday |
|
| |
for the amount of time programmed into the |
|
|
countdown timer for the specific relay (Block |
|
|
7, CL 013 - 034). |
|
|
Timed Relay Closing (Timer #2 - Day of Week)
Cmd Loc 070
Default 0
Range 0 - 127
Timed Relay Closing (Timer #2 - Hours)
Cmd Loc 071
Default 0
Range 0 - 23
Timed Relay Closing (Timer #2 - Minutes)
Cmd Loc | 072 |
Default | 0 |
Range | 0 - 59 |
Comments | Options: (CL 070) | |
These Options will determine the Day(s) of | 0 | Disabled |
the Week and Time of Day when the pro- | 1 | Saturday |
grammed relay will automatically close. The | 2 | Friday |
value programmed into CL 070 is the total for | 4 | Thursday |
all days the relay is to be activated. The relay | 8 | Wednesday |
to be closed is programmed in Block 7, CL | 16 | Tuesday |
001 - 011 using Option 80. | 32 | Monday |
Once activated, the relay will remain closed | 64 | Sunday |
|
| |
for the amount of time programmed into the |
|
|
countdown timer for the specific relay (Block |
|
|
7, CL 013 - 034). |
|
|
Timed Relay Closing (Timer #3 - Day of Week)
Cmd Loc 073
Default 0
Range 0 - 127
Timed Relay Closing (Timer #3 - Hours)
Cmd Loc | 074 |
Default | 0 |
Range | 0 - 23 |
Timed Relay Closing (Timer #3 - Minutes)
Cmd Loc 075
Default 0
Range 0 - 59
Comments | Options: (CL 073) | |
These Options will determine the Day(s) of | 0 | Disabled |
the Week and Time of Day when the pro- | 1 | Saturday |
grammed relay will automatically close. The | 2 | Friday |
value programmed into CL 073 is the total for | 4 | Thursday |
all days the relay is to be activated. The relay | 8 | Wednesday |
to be closed is programmed in Block 7, CL | 16 | Tuesday |
001 - 011 using Option 81. | 32 | Monday |
Once activated, the relay will remain closed | 64 | Sunday |
|
| |
for the amount of time programmed into the |
|
|
countdown timer for the specific relay (Block 7, CL 013 - 034).
Timed Relay Closing (Timer #4 - Day of Week)
Cmd Loc | 076 |
Default | 0 |
Range | 0 - 127 |
Timed Relay Closing (Timer #4 - Hours)
Cmd Loc | 077 |
Default | 0 |
Range | 0 - 23 |
Timed Relay Closing (Timer #4 - Minutes)
Cmd Loc 078
Default 0
Range 0 - 59
Comments | Options: (CL 076) | |
These Options will determine the Day(s) of | 0 | Disabled |
the Week and Time of Day when the pro- | 1 | Saturday |
grammed relay will automatically close. The | 2 | Friday |
value programmed into CL 076 is the total for | 4 | Thursday |
all days the relay is to be activated. The relay | 8 | Wednesday |
to be closed is programmed in Block 7, CL | 16 | Tuesday |
001 - 011 using Option 82. | 32 | Monday |
Once activated, the relay will remain closed | 64 | Sunday |
|
| |
for the amount of time programmed into the |
|
|
countdown timer for the specific relay (Block |
|
|
7, CL 013 - 034). |
|
|
Number of REMMs
Cmd Loc | 079 |
Default | 0 |
Range | 0 - 2 |
|
|
Comments
This option determines where panel events are stored. 0 = No REMMs installed, all events are stored in the control panel’s event memory (60 events maxi-
mum).
1 = REMM #1 installed. Control panel events will be stored in the REMM (250 events maximum).
2 = Both REMM #1 and REMM #2 are installed. Control panel events will be stored using a both REMMs (500 events maximum).
Options:
0None
1REMM 1 only
2 REMM 1 and 2