Block 7 - Auxiliary Devices Programming (cont.)

Timer Units (REMM #2, Relay #1)

Cmd Loc 025

Default 2

Range 1 - 5

Timer Count (REMM #2, Relay #1)

Cmd Loc 026

Default 30

Range 1 - 255

Comments

Options:

For REMM #2, Relay #1, CL 025 stores the units, while

1

Latched

CL 026 stores the starting count. The timer will count

2

Seconds

backwards and when it reaches 0, the respective relay

3

Minutes

will open.

4

Hours

 

5

Days

NOTE: The timer function is ignored if the Relay option (Block 7, CL 001 -

011)is programmed for SpreadNet Arming/Disarming (option #5), Listen-In Trigger (option #9), Follows Keypad Sounder (option #10), Relay Status #1 (option #67), Relay Status #2 (option #68), 3-second Toggle for Audible Shutoff (option #72), or 3-second Toggle for Local Bell Test (option #73).

Timer Units (REMM #8, Relay #2)

Cmd Loc 027

Default 2

Range 1 - 5

Timer Count (REMM #2, Relay #2)

Cmd Loc 028

Default 30

Range 1 - 255

Timer Units (REMM #2, Relay #3)

Cmd Loc 029

Default 2

Range 1 - 5

Timer Count (REMM #2, Relay #3)

Cmd Loc

030

Default

30

Range

1 - 255

Comments

For REMM #2, Relay #2, CL 027 stores the units, while CL 028 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.

Comments

For REMM #2, Relay #3, CL 029 stores the units, while CL 030 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.

Timer Units (REMM #2, Relay #4)

Cmd Loc 031

Default 2

Range 1 - 5

Timer Count (REMM #2, Relay #4)

Cmd Loc 032

Default 30

Range 1 - 255

Timer Units (REMM #2, Relay #5)

Cmd Loc

033

Default

2

Range

1 - 5

Timer Count (REMM #2, Relay #5)

Cmd Loc 034

Default 30

Range 1 - 255

Comments

For REMM #2, Relay #4, CL 031 stores the units, while CL 032 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.

Comments

For REMM #2, Relay #5, CL 033 stores the units, while CL 034 stores the starting count. The timer will count backwards and when it reaches 0, the respective relay will open.

Relay Activation By Zone (Zones 1 - 32)

Cmd Loc

035

036

037

038

039

040

041

042

Zone #

1

2

3

4

5

6

7

8

Cmd Loc

043

044

045

046

047

048

049

050

Zone #

9

10

11

12

13

14

15

16

Cmd Loc

051

052

053

054

055

056

057

058

Zone #

17

18

19

20

21

22

23

24

Cmd Loc

059

060

061

062

063

064

065

066

Zone #

25

26

27

28

29

30

31

32

Default

0 (All CL)

 

 

 

 

 

 

Range

0 - 11 (All CL)

 

 

 

 

 

Comments

These Options determine which relay(s) are activated following an alarm on a specific zone. Each relay may be specified by one or more zones.

The specific relay (Block 7, CL 001 - 011) must be programmed for zone activation (Op- tion #74).

Options:

0No Relay Activation

1 On Board Relay

2 REMM #1, Relay #1

3 REMM #1, Relay #2

4 REMM #1, Relay #3

5 REMM #1, Relay #4

6 REMM #1, Relay #5

7 REMM #2, Relay #1

8 REMM #2, Relay #2

9 REMM #2, Relay #3

10REMM #2, Relay #4

11REMM #2, Relay #5

33