Country Specific Compliance Information

Singapore

The following hardware and programming guidelines are required for installation of this system in Singapore.

Hardware Requirements:

1. The Digital Communicator must be Model S5070SG or S5070SG-2.

Programming Requirements:

1.Dial Type (Block 4, CL 101) must be programmed for DTMF only.

2.Dial Attempts (Block 4, CL 102) must not be programmed to more than 10.

Malaysia

The following hardware and programming guidelines are required for installation of this system in Malaysia.

Hardware Requirements:

1. The Digital Communicator must be Model S5070SG or S5070SG-2.

Programming Requirements:

1.Dial Attempts (Block 4, CL 102) must not be programmed to more than 3.

Standby Battery Information

The Table and worksheet below provide the installer with the infor- mation necessary to determine the AH rating and battery require- ments for any particular installation.

Sierra Accessory Loading

Product current consumption

 

Max. Standby

Max. Active

 

 

 

 

S5832 Control Panel

 

125 mA

125 mA

S5010

Alpha Keypad

 

30 mA

50 mA

S5020 LED Keypad

 

30 mA

50 mA

 

 

 

 

 

S5030

Icon Keypad

 

30 mA

50 mA

 

 

 

 

 

S5050

REMM (up to 2)

 

100 mA (each)

100 mA

S5058 ZEM (up to 3)

 

40 mA (each)

40 mA**

 

 

 

 

S5070 Single-line Dialer

 

35 mA

60 mA

 

 

 

 

S5070-2 Dual-line Dialer

 

35 mA

70 mA

 

 

 

 

SN915-BUS RF Receiver

 

125 mA

170 mA

**ZEM VOUT terminals can supply up to 300 mA (max.)

 

 

 

 

Table A - Standby Battery Loading

 

 

AH Requirements for Backup

Product/Device

4-Hour

24-Hour

72-Hour

Qty

Total

 

 

 

 

 

 

S5832SG

0.5 AH

3.0 AH

9.0 AH

 

 

S5010

0.12 AH

0.72 AH

2.16 AH

 

 

 

 

 

 

 

 

S5020

0.12 AH

0.72 AH

2.16 AH

 

 

 

 

 

 

 

 

S5030

0.12 AH

0.72 AH

2.16 AH

 

 

S5050

0.4 AH

2.4 AH

7.2 AH

 

 

 

 

 

 

 

 

S5058

0.16 AH

0.96 AH

2.88 AH

 

 

 

 

 

 

 

 

S5070(-2)

0.14 AH

0.84 AH

2.52 AH

 

 

 

 

 

 

 

 

SN915-BUS

0.5 AH

3.0 AH

9.0 AH

 

 

 

 

 

 

 

 

Sensor (10 mA)

0.04 AH

0.24 AH

0.72 AH

 

 

Sensor (25 mA)

0.1 AH

0.6 AH

1.8 AH

 

 

Bell/Siren (5 min)

0.085 AH

0.085 AH

0.085 AH

 

 

Bell/Siren (15 min)

0.225 AH

0.225 AH

0.225 AH

 

 

 

 

 

 

 

 

* Bell/Siren current may be 0.7 - 1.0 A

Total AH Required

 

 

 

 

 

 

 

Table B - AH Requirements

Determining Standby Battery Requirements

To calculate the size (AH rating) of your system's Backup Battery, enter the Number (Qty) of devices of each type in the chart above. Multiply the number of devices times the AH rating for the desired backup period (Qty x AH = Total) and enter the total in the last column. To determine the total AH rating of the battery, add all values in the last column.

Total current from all sensors must be considered when calculat- ing AH rating. For example:

10 sensors @ 10 mA = 100 mA

4 sensors @ 25 mA = 100 mA Total current all sensors = 200 mA

i