Toshiba RAV-SM800XT-E Specification Of Electrical Parts, Indoor Unit, Outdoor Unit RAV-SM560AT-E

Models: RAV-SM560XT-E RAV-SM800XT-E

1 88
Download 88 pages 43.27 Kb
Page 14
Image 14

5. SPECIFICATION OF ELECTRICAL PARTS

5-1. Indoor Unit

No.

Parts name

Type

Specifications

 

 

 

 

1

Fan motor (for indoor)

AFP-220-50-4A

Output (Rated) 50 W, 220 – 240 V

 

 

 

 

2

Grille motor

MP35EA12

DC 12 V

 

 

 

 

3

Thermo. sensor (TA-sensor)

550 mm

10 kat 25°C

 

 

 

 

4

Heat exchanger sensor (TC-sensor)

6 mm, 500 mm

10 kat 25°C

 

 

 

 

5

Heat exchanger sensor (TCJ-sensor)

6 mm, 500 mm

10 kat 25°C

 

 

 

 

5-2. Outdoor Unit (RAV-SM560AT-E)

No.

Parts name

Type

Specifications

 

 

 

 

1

Fan motor

ICF-140-43-1

Output (Rated) 40 W

 

 

 

 

2

Compressor

DA130A1F-23F

3 phase, 4P, 1100 W

 

 

 

 

3

Reactor

CH-57

1=10 mH, 16A

 

 

 

 

4

Outdoor temp. sensor (To-sensor)

10 kat 25°C

 

 

 

 

5

Heat exchanger sensor (Te-sensor)

10 kat 25°C

 

 

 

 

6

Suction temp. sensor (Ts-sensor)

10 kat 25°C

 

 

 

 

7

Discharge temp. sensor (Td-sensor)

50 kat 25°C

 

 

 

 

8

Fuse (Switching power (Protect))

T3.15 A, AC 250 V

 

 

 

 

9

Fuse (Inverter, input (Current protect)

25 A, AC 250 V

 

 

 

 

10

4-way valve solenoid coil

STF-0108G

 

 

 

 

 

11

Compressor thermo. (Protection)

US-622

ON : 90 ± 5°C, OFF : 125 ± 4°C

 

 

 

 

5-3. Outdoor Unit (RAV-SM800AT-E)

No.

Parts name

Type

Specifications

 

 

 

 

1

Fan motor

ICF-140-63-1

Output (Rated) 63 W, 220 – 240 V

 

 

 

 

2

Compressor

DA220A2F-20L

3 phase, 4P, 1600 W

 

 

 

 

3

Reactor

CH-47

 

 

 

 

 

4

Outdoor temp. sensor (To-sensor)

10 kat 25°C

 

 

 

 

5

Heat exchanger sensor (Te-sensor)

10 kat 25°C

 

 

 

 

6

Suction temp. sensor (Ts-sensor)

10 kat 25°C

 

 

 

 

7

Discharge temp. sensor (Td-sensor)

50 kat 25°C

 

 

 

 

8

Fuse (Switching power (Protect))

T3.15 A, AC 250 V

 

 

 

 

9

Fuse (Inverter, input (Current protect)

25 A, AC 250 V

 

 

 

 

10

4-way valve solenoid coil

DKV-M0ZS743B0

 

 

 

 

 

11

Compressor thermo. (Protection)

US-622

ON : 90 ± 5°C, OFF : 125 ± 4°C

 

 

 

 

– 12 –

Page 14
Image 14
Toshiba RAV-SM800XT-E, RAV-SM560XT-E Specification Of Electrical Parts, Indoor Unit, Outdoor Unit RAV-SM560AT-E