Table 10-2-1

 

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

 

 

Judgement and action

Check

Block

Check

Symptom

Unit

Condition

 

code

code

status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

The indoor thermo sensor (TA) is

Operation

The lamp on the

1.

Check the indoor thermo sensor (TA).

 

P.C. board

 

defective.

continues.

indoor unit blinks

2.

Check the indoor P.C. board.

 

 

 

Disconnection or short-circuit

 

when error is

 

 

 

 

 

 

 

defected.

 

 

 

 

 

 

 

 

 

 

 

 

 

The indoor heat exchanger

Operation

The lamp on the

1.

Check the indoor heat exchanger

 

 

 

sensor (TC) is defective.

continues.

indoor unit blinks

 

sensor (TC).

 

 

 

Disconnection or short-circuit

 

when error is

2.

Check the indoor P.C. board.

 

 

 

 

 

defected.

 

 

 

 

 

 

 

 

 

 

 

 

 

The indoor fan motor or its circuit

All off

The lamp on the

1.

Check the connector circuit of the

 

 

 

is defective.

 

indoor unit blinks

 

indoor fan motor (CN10).

 

 

 

 

 

when error is

2.

Check the indoor fan motor.

 

 

 

 

 

defected.

3. Check the indoor P.C. board.

 

 

 

The part other than the above

Operation

The lamp on the

1.

Check the indoor P.C. board.

 

 

 

parts on the indoor P.C. board is

continues.

indoor unit blinks

 

(EEPROM and peripheral circuits)

 

 

 

defective.

 

when error is

 

 

 

 

 

EEPROM access error

 

defected.

 

 

 

 

 

IOL operation

All off

The lamp on the

Overload operation of refrigerating cycle

 

 

 

 

 

indoor unit blinks

 

 

 

 

 

 

 

when error is

 

 

 

 

 

 

 

defected.

 

 

 

The block is

 

The variation of TC, 5 minutes

Operation

The lamp on the

1.

Check whether or not the TC sensor

 

unidentifi-

 

after starting the compressor,

continues.

indoor unit blinks

 

comes off.

 

able

 

is 2K or less.

 

when error is

2.

Check whether or not it is possible to

 

 

 

 

 

defected.

 

operate the compressor and the

 

 

 

 

 

 

 

outdoor fan motor.

 

 

 

 

 

 

3.

Check gas leak.

 

Cable

 

The serial signals can not be

Operation

The lamp on the

1.

In the case of the outdoor unit not

 

connection

 

transmitted and received between

continues.

indoor unit blinks

 

operating at all;

 

 

 

indoor and outdoor units.

 

when error is

 

Check the crossover cable and

 

 

 

The crossover wire is

 

defected.

 

connect it properly.

 

 

 

connected wrongly.

 

 

 

Check the outdoor P.C. board.

 

 

 

The serial signal transmitting

 

 

2.

In the case of the outdoor unit operating

 

 

 

circuit on the outdoor P.C. board

 

 

 

normally;

 

 

 

is defective.

 

 

 

Check whether or not both of serial

 

 

 

The serial signal receiving

 

 

 

LED (Green) and serial LED (Orange)

 

 

 

circuit on the indoor P.C. board

 

 

 

is blinking.

 

 

 

is defective.

 

 

 

If the serial LED (Green) is not

 

 

 

 

 

 

 

blinking, check the outdoor P.C. board.

 

 

 

 

 

 

 

If the serial LED (Orange) is not

 

 

 

 

 

 

 

blinking, check the indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

The operation command signals

Operation

The lamp on the

If the operation command signals continue

 

 

 

are not transmitted from the

continues.

indoor unit blinks

to be transmitted between 2 and 3 of the

 

 

 

indoor unit to the outdoor unit.

 

when error is

indoor terminal block, replace the outdoor

 

 

 

 

 

defected. And it

P.C. board.

 

 

 

 

 

returns to the

 

 

 

 

 

 

 

normal condition

 

 

 

 

 

 

 

when recovering

 

 

 

 

 

 

 

from errors.

 

 

 

Outdoor

 

The outdoor thermo sensor (TE)

All off

The lamp on the

1.

Check the outdoor thermo sensor (TE).

 

P.C. board

 

is defective.

 

indoor unit blinks

2.

Check the outdoor P.C. board.

 

 

 

Disconnection or short-circuit

 

when error is

 

 

 

 

 

 

 

defected.

 

 

 

 

 

The outdoor heat exchanger (TD)

All off

The lamp on the

1.

Check the outdoor heat exchanger

 

 

 

sensor is defective.

 

indoor unit blinks

 

sensor (TD).

 

 

 

Disconnection or short-circuit

 

when error is

2.

Check the outdoor P.C. board.

 

 

 

 

 

defected.

 

 

 

 

 

 

 

 

 

 

 

Other parts

 

The reply serial signal has been

Operation

The lamp on the

1.

Repeatedly turn the indoor unit on and

 

(including

 

transmitted when starting the

continues.

indoor unit blinks

 

off with the interval of approx. 10 to 40

 

compressor)

 

unit, but stops being transmitted

 

when error is

 

minutes. (The check code is not

 

 

 

shortly after.

 

defected. And it

 

indicated during operation.) And supply

 

 

 

1. Compressor thermo operation

 

returns to the

 

gas. (Check gas leak.)

 

 

 

Gas shortage

 

normal condition

2.

The indoor unit operates normally

 

 

 

Gas leak

 

when recovering

 

during the check.

 

 

 

2. Instantaneous power failure

 

from errors.

 

If the reply serial signal continues to be

 

 

 

 

 

 

 

transmitted between 2 and 3 of the

 

 

 

 

 

 

 

indoor terminal block, replace the

 

 

 

 

 

 

 

outdoor P.C. board.

 

 

 

 

 

 

 

If the signal stops between them,

 

 

 

 

 

 

 

replace the indoor P.C. board.

 

 

 

The discharge temperature is

All off

The lamp on the

1.

Check the heat exchanger sensor (TD).

 

 

 

over 120°C.

 

indoor unit blinks

2.

Gas purging

 

 

 

 

 

when error is

 

 

 

 

 

 

 

defected.

 

 

 

 

 

 

 

 

 

 

 

 

The IOL operation is defective.

All off

The lamp on the

When turning on the unit, the normal

 

 

 

 

 

indoor unit blinks

phase (RST) is detected but T-R waveform

 

 

 

 

 

when error is

has not been detected for 120 seconds or

 

 

 

 

 

detected.

more.

 

 

 

 

 

 

 

 