Toshiba RAV-SM560XT-E, RAV-SM800XT-E service manual Outdoor Unit

Models: RAV-SM560XT-E RAV-SM800XT-E

1 88
Download 88 pages 43.27 Kb
Page 5
Image 5

1-2. Outdoor Unit

Model name

 

 

 

RAV-SM560AT-E

 

RAV-SM800AT-E

 

 

 

 

 

 

 

Appearance

 

 

 

Silky shade (Muncel 1Y8.5/0.5)

 

 

 

 

 

 

 

Power supply

 

 

 

1 phase 230V (220 – 240V) 50Hz

 

 

 

(Power exclusive to outdoor is required.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

Hermetic compressor

 

 

 

 

 

 

 

 

Compressor

 

Motor

(kW)

1.1

 

1.6

 

 

 

 

 

 

 

 

 

 

Pole

 

 

4 poles

 

 

 

 

 

 

 

Refrigerant charged

(kg)

R410A 0.9

 

R410A 1.5

 

 

 

 

 

 

Refrigerant control

 

Pulse motor valve

 

 

 

 

 

 

 

 

 

Standard length

 

20 (without additional charge)

 

 

 

 

 

 

 

 

 

 

Max. total length

(m)

30

 

50

 

 

 

 

 

 

 

 

Pipe

 

Over 20m

 

Add 20g/m (Max. 200g)

 

Add 40g/m (Max. 1200g)

 

 

 

 

 

 

 

 

 

 

Height difference

Outdoor lower

(m)

 

15

 

 

 

 

 

 

 

 

 

Outdoor higher

(m)

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

(mm)

595

 

795

Outer

 

 

 

 

 

 

 

 

Width

(mm)

780

 

780

dimension

 

 

 

 

 

 

 

 

 

 

 

Depth

(mm)

270

 

270

 

 

 

 

 

 

 

 

Total weight

 

 

(kg)

35

 

55

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

Fan

 

 

Propeller fan

 

 

 

 

 

 

 

 

Fan unit

 

Standard air flow High

(m³/h)

2400

 

3400

 

 

 

 

 

 

 

 

 

 

Motor

(W)

43

 

63

 

 

 

 

 

 

 

 

Connecting

 

Gas side

(mm)

Ø12.7 (1/2”)

 

Ø15.9 (5/8”)

 

 

 

 

 

 

 

pipe

 

Liquid side

(mm)

Ø6.4 (1/4”)

 

Ø9.5 (3/8”)

 

 

 

 

 

 

 

 

 

 

Protection device

 

Discharge temp. sensor

 

Over-current sensor

 

 

 

 

 

Compressor thermo.

 

 

 

 

 

 

 

 

Sound level

 

High (Mid./Low)

(dB•A)

46/48

 

48/50

(Note 2)

 

(Cooling/Heating)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

Note 2 : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB

– 3 –

Page 5
Image 5
Toshiba RAV-SM560XT-E, RAV-SM800XT-E service manual Outdoor Unit