<Inspection procedure>

-Cooling and heating model-

Turn on power supply.

Does OPERATION

NO

lamp blink?

 

 

 

YES

 

 

 

 

 

 

 

 

NO

Is it possible to start

 

unit by remote control?

YES

Is it possible to detect

NO

DC 15 60 V between

 

2and 3 on terminal block?

YES

Refer to item Power can not be turned on.

Refer to 9-9 Troubleshooting for Remote Control.

Check TA and TC sensors

or refer to 01 04 in Table 9-4-1.

Is crossover cable normal?

NO

Connect crossover

cable properly.

 

YES

 

 

 

 

 

 

 

 

 

 

Is it possible to detect

NO

AC 12 V on secondary side

 

 

(CN06) of transformer?

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Is it possible to detect

DC 5 V at Q60 and 12 V at Q50?

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

All lamps on

 

 

indoor unit normal?

 

 

 

 

 

 

YES

 

 

 

 

Are TD and TE sensors normal?

NO

(TD=17.9 kat 50°C)

 

 

 

 

(TE=10 kat 25°C)

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Is it possible to detect

AC 220 240 V at CN11?

YES

NO

Does MG switch operate?

(Next Page)

Replace outdoor transformer.

Replace outdoor

P.C. board.

Refer to item 9-8-3How to check outdoor P.C. board.

Replace sensors.

Replace outdoor

P.C. board.

Replace MG switch.

– 58 –