9-10. FINAL INSTALLATION CHECKS
|
| ||||||
Ensure that the electrical cable used for power supply | To switch the TEST RUN (COOL) mode, press | ||||||
and control of the system is unable to come into | TEMPORARY button for 10 sec. | ||||||
contact with either service valves or piping work which | (The beeper will make a short beep.) | ||||||
are not insulated. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
When installation is complete, check that all power |
|
|
|
|
|
|
|
supply and interconnecting wiring has been |
|
|
|
|
|
|
|
appropriately protected. |
|
|
|
|
|
|
|
9-10-3. Refrigerant piping
When refrigerant and drain piping have been completed. Ensure that all pipework is fully insulated and apply finishing tape to seal the insulation.
9-10-4. Check and Test Operation
•Pressure of R410A is approx. 1.6 times of that of R22. If installation work is incompletely finished, a gas leakage may occur at the cases such as pressure rise during operation.
Therefore, be sure to test the piping connections for leakage.
•Check the flare nut connections, valve stem cap connections and service port cap fittings for gas leak with a leak detector or soap water.
Piping cover |
|
Cord clamp |
|
Indoor/Outdoor | Flare nut |
connecting | connections |
cables | (Indoor unit) |
Power cable |
|
| Valve cover |
Fig.
Hi POWER FILTER PRE.D
TEMPORARY button
Fig. 9-10-2
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the Auto Restart>
•Press and hold the TEMPORARY button for about 3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
•To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the Owner’s Manual.
– 43 –