10-3. Troubleshooting for Each Check Code

10-3. Troubleshooting for Each Check Code

[1A error]

Are connections of CN301 and

 

CN300 of CDB correct?

 

YES

 

Does the fan rotate without trouble

NO

when handling the fan with hands under condition

 

of removing CN301 and CN300 from CDB?

 

YES

 

The status that the resistance values

 

between leads below are 50 to 80

 

for 40 W motor (ICF-140-43) and 25 to 55

NO

for 60 W motor (ICF-140-63-1) is normal.

 

Between 1 (Red lead) and 2 (White lead)

 

Between 2 (White lead) and 3 (Black lead)

 

Between 3 (Black lead) and 1 (Red lead)

 

of motor winding of connector (CN301)

 

YES

 

The status that there is

 

5k to 20kresistance values between

NO

1 (Yellow lead) and 4 (Pink lead)

 

of motor position detection of connector

 

(CN300, CN302) is normal.

 

YES

 

CN301

CN300

For RAV-SM560AT-E, CN300 changes to CN301, and CN301 to CN300, respectively.

Normal fan motor

(CDB error)

Defective fan motor

NOTE :

However, GND circuit error inside of the motor is rarely detected even if the above check is carried out. When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.

 

RAV-SM560AT-E

RAV-SM800AT-E

 

 

 

Objective P.C. board

Control P.C. board

CDB P.C. board

 

 

 

Fan motor winding

CN300

CN301

 

 

 

Motor position detection

CN301

CN300

 

 

 

– 51 –