9-3. Accessory parts and Parts to be procured locally

9-3-1. Accessory parts

Part

Part name

Q’ty

Shape

No

 

 

 

1

Installation plate

1

 

2

Installation Manual

1

 

3

Owner’s Manual

1

 

4

Mounting screw

8

 

4 x 25 S

 

5

Flexible pipe

1

 

 

Drain nipple

 

 

6

(Packaged with the

1

 

 

outdoor unit)

 

 

Part

Part name

Q’ty

Shape

No

 

 

 

8

Purifying filter

1

 

9

Filter frame

2

 

!

Battery

2

 

"

Remote controller

1

 

 

holder

 

 

#

Pan head wood

2

 

screw 3.1 x 16 S

 

$

Pipe shield

1

 

%

controllerWireless remote

1

 

7

Zeolite filter

1

9-3-2. Parts to be procured locally

Connecting pipe (Liquid side)

(6.35 mm (diam.), Nominal (diam.) 1/4" thick 0.8 mm) RAV-SM560XT-E, RAV-SM560AT-E

(9.52 mm (diam.), Nominal (diam.) 3/8" thick 0.8 mm) RAV-SM800XT-E, RAV-SM800AT-E

Connecting pipe (Gas side)

(12.7 mm (diam.), Nominal (diam.) 1/2" thick 0.8 mm) RAV-SM560XT-E, RAV-SM560AT-E

(15.9 mm (diam.), Nominal (diam.) 5/8" thick 1.0 mm) RAV-SM800XT-E, RAV-SM800AT-E

Power supply cord

2.5 mm2 (H07RN-F or 245IEC66) or 3.5 mm2 (AWG-12)

Connecting cable

H07RN-F or 245IEC66 (1.5 mm2 or more)

Thermal insulation for refrigerant pipe

(10 mm or more, thermal insulating foam polyethylene)

Thermal insulation for drain pipe

(10 mm or more, foam polyethylene)

Drain pipe (Outer 26 mm (diam.))

Tapes

Grounding cable (2.0 mm (diam.) or more)

– 30 –

Page 32
Image 32
Toshiba RAV-SM800XT-E, RAV-SM560XT-E service manual Accessory parts and Parts to be procured locally