Toshiba RAV-SM800XT-E, RAV-SM560XT-E service manual error

Models: RAV-SM560XT-E RAV-SM800XT-E

1 88
Download 88 pages 43.27 Kb
Page 54
Image 54
[14 error]

[14 error]

NO

Is power voltage normal?

YES

Improve the power supply line.

Are connections of

NO

 

cabling/connector normal?

 

YES

*For RAV-SM560AT-E,

check RY01 on the control P.C. board.

Check and correct circuit cables. Correct connection of connector. Check and correct reactor connection.

Does RY01 relay of

YES

Is not 14 errors output

NO

 

 

when an operation is performed by

 

IPDU operate?

 

 

 

 

 

removing 3P connector of compressor?

 

 

 

 

 

NO

 

 

YES

 

 

 

 

 

*Single-phase type is not provided to RAV-SM560AT-E.

 

 

 

YES

 

 

 

 

 

Replace IPDU.

 

 

 

 

 

 

 

Is not AC fuse fused?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

* Replace control P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of RAV-SM560AT-E.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace IPDU.

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

Is compressor normal?

 

 

 

 

 

 

 

 

 

 

 

 

* Replace control P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of RAV-SM560AT-E.

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check IPDU.

 

 

 

Check rare short of compressor trouble.

 

 

 

 

 

 

 

Defect Replace

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[16 error]

Are connections of

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

cable/connector normal?

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

Is compressor normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is not earthed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

Is not winding shorted?

 

 

 

 

 

 

 

 

 

(Is resistance between windings 0.6 to 1.2 ?)

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

Is not winding opened?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check IPDU P.C. board

 

 

 

 

 

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check and correct circuit cabling such as cabling to compressor.

Compressor error [16 error] Replace

Compressor error – 52 – Replace

Compressor error Manual background Replace

– 52 –