10-4 Compressor does not operate.

<Primary check>

(1)Is the preset temperature higher than the room temperature in cooling operation?

(2)Is the crossover cable connected properly?

<Inspection procedure>

-Cooling only model-

Turn on power supply.

Does OPERATION lamp blink?

YES

Does miniature relay RY04

switch on and off due to temperature changes?

YES

Is it possible to detect

AC 220 240 V between

2and 3 on the terminal block?

YES

Are all of compressor cords normal?

YES

Is compressor motor

winding normal? (Check winding resistor.)

YES

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

Refer to 9-6-1 Power

 

 

 

 

 

 

 

 

 

 

 

 

 

can not be turned on .

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Is resistance value of thermo

NO

 

Thermo sensor or heat

 

sensor (TA) and heat exchanger

 

exchanger sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

sensor (TC) normal?

 

 

 

 

is defective.

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Microcontroller is defective.

 

 

 

 

 

 

 

 

 

Replace thermo

 

 

 

 

 

 

 

 

 

 

 

 

sensor or heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

exchanger sensor.

 

 

Miniature relay RY04 is defective.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace P.C. board.

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rewire or replace

 

 

NO

 

Compressor is defective.

 

 

 

 

 

 

 

 

defective cords.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is capacitor for

NO

Capacitor is defective.

compressor normal?

 

 

 

 

YES

 

 

 

 

 

 

 

NO

 

Is overload relay normal?

Overload relay is defective.

 

 

YES

 

 

 

 

 

 

 

NO

 

Does compressor start?

Compressor is defective.

 

 

YES

 

 

 

 

 

 

 

 

 

Does compressor stop

 

 

after a while?

 

 

 

YES

 

 

 

 

 

 

 

NO

 

Is gas quantity normal?

Gas shortage (Gas leak)

(Check gas pressure.)

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

Compressor is defective.

 

 

 

YES

 

 

 

 

 

 

 

 

 

Replace capacitor.

Replace overload relay.

Replace compressor.

Supply gas.

Replace P.C. board.

– 57 –