10-4 Compressor does not operate.
<Primary check>
(1)Is the preset temperature higher than the room temperature in cooling operation?
(2)Is the crossover cable connected properly?
<Inspection procedure>
Turn on power supply.
Does OPERATION lamp blink?
YES
Does miniature relay RY04
switch on and off due to temperature changes?
YES
Is it possible to detect
AC 220 − 240 V between
2and 3 on the terminal block?
YES
Are all of compressor cords normal?
YES
Is compressor motor
winding normal? (Check winding resistor.)
YES
| NO |
|
|
|
|
|
|
|
|
|
|
|
| Refer to | |||
|
|
|
|
|
|
|
|
|
|
|
|
| can not be turned on . | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| NO | Is resistance value of thermo | NO |
| Thermo sensor or heat | ||||||||||||
| sensor (TA) and heat exchanger |
| exchanger sensor |
|
|
| |||||||||||
|
|
|
|
|
|
|
| ||||||||||
|
| sensor (TC) normal? |
|
|
|
| is defective. |
|
| ||||||||
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Microcontroller is defective. |
|
|
|
|
|
|
|
|
| Replace thermo |
| ||||
|
|
|
|
|
|
|
|
|
|
| sensor or heat |
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| NO |
|
|
|
|
|
|
|
|
|
|
|
| exchanger sensor. |
| ||
| Miniature relay RY04 is defective. |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Replace P.C. board. |
| ||
| NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| Rewire or replace |
| |||
| NO |
| Compressor is defective. |
|
|
|
|
|
|
|
| defective cords. |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| Replace compressor. |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Is capacitor for | NO | Capacitor is defective. | ||
compressor normal? |
| |||
|
| |||
| YES |
|
| |
|
|
| ||
|
| NO |
| |
Is overload relay normal? | Overload relay is defective. | |||
| ||||
| YES |
|
| |
|
|
| ||
|
| NO |
| |
Does compressor start? | Compressor is defective. | |||
| ||||
| YES |
|
| |
|
|
| ||
|
|
|
| |
Does compressor stop |
|
| ||
after a while? |
|
| ||
| YES |
|
| |
|
|
| ||
|
| NO |
| |
Is gas quantity normal? | Gas shortage (Gas leak) | |||
(Check gas pressure.) |
| |||
|
| |||
| YES |
|
| |
|
|
| ||
|
|
|
| |
Compressor is defective. |
|
| ||
| YES |
|
| |
|
|
| ||
|
|
|
|
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.
Replace P.C. board.