[18 error]
Are connections of
TE/TS sensor connectors of
CDB CN604/CN605 normal?
YES
Are characteristics of TE/TS sensor resistance values normal?
YES
NO
Correct connection of connector.
* (For
NO
Replace TE and TS sensors.
* Refer to
Check CDB. Defect Replace
* For
[19 error]
Is connection of TD sensor connector
of CDB CN600 normal?
YES
Are characteristics of TD sensor resistance value normal?
YES
NO
Correct connection of connector.
* (For
NO
Replace TD sensors.
|
|
|
|
|
| Check control P.C. board. |
| * Refer to | |
| Defect | Replace |
| |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
[1C error]* Except RAV-SM560AT-E
Are connections of | NO | ||
CDB CN800 and CDB IPDU CN06 | |||
| |||
| |||
connectors normal? |
| ||
| YES |
| |
|
| ||
|
|
|
Correct connection of connector.
Was the error just after power ON determined?
NO
Is there no abnormal overload?
NO
YES | Are cabling/connector normal? | NO | |
|
| ||
|
| ||
|
| YES | |
|
| ||
|
|
|
|
YES
Check cabling between IPDU and CDB and connector.
IPDU P.C. board error
Defect Replace
Improve and eliminate the cause.
Is IPDU P.C. board come to | NO | |
| ||
closely contact with heat sink? |
| |
| YES |
|
|
| |
|
|
|
Correct mounting.
IPDU P.C. board error Defect Replace