Installation

Voltage and MPPT Requirements

MPPT operational

Ensure that the PV array used in the system operates within the MPPT operational

window

window (Table 2-1).

 

 

 

Table 2-1MPPT Operational Window

 

 

 

Voltage

 

Effect of Array Voltage

 

Inverter Mode

 

 

 

 

 

 

 

 

 

 

< 195 Vdc

 

Operating voltage will be shifted to 195 Vdc;

 

Low power

 

 

 

the array will not be at its maximum power

 

 

 

 

 

point

 

 

 

 

 

 

 

 

 

195 to 550 Vdc

 

Maximum harvest of solar energy

 

MPPT window

 

 

 

 

 

 

 

550 to 600 Vdc

 

Will not allow maximum harvest of solar

 

Power derating

 

 

 

energy

 

 

 

 

 

 

 

 

 

> 600

 

Will shut down and may cause damage to the

 

Shutdown

 

 

 

inverter; stops selling surplus energy

 

 

 

 

 

 

 

 

Voltage

The maximum power point voltage of a string connected to the GT Inverter should

requirements

be a minimum of 195 Vdc. If it is less than 195 Vdc, then the power point is

 

shifted and the PV voltage is regulated to 195 Vdc.

 

 

 

By regulating the operating voltage of the solar modules, the MPPT software

 

maximizes their output energy.

 

 

 

Effects of array voltages outside of the MPPT operational window are shown in

 

Table 2-1.

 

 

 

 

Maximum PV

The solar array should be sized such that its maximum power output does not

Power

exceed the limits of the MPPT operational window (195 to 550 Vdc). See

 

“Guidelines for Matching PV Array Size to Xantrex Grid Tie Solar Inverter

 

Input”.

 

 

 

 

Under no conditions should the array voltage exceed 600 VOC (open circuit voltage).

2–6

975-0131-01-01