Installation
Voltage and MPPT Requirements
| MPPT operational | Ensure that the PV array used in the system operates within the MPPT operational | ||||
| window | window (Table  | 
 | 
 | ||
| 
 | Table  | 
 | 
 | ||
| 
 | Voltage | 
 | Effect of Array Voltage | 
 | Inverter Mode | 
| 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | < 195 Vdc | 
 | Operating voltage will be shifted to 195 Vdc; | 
 | Low power | 
| 
 | 
 | 
 | the array will not be at its maximum power | 
 | 
 | 
| 
 | 
 | 
 | point | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 195 to 550 Vdc | 
 | Maximum harvest of solar energy | 
 | MPPT window | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 550 to 600 Vdc | 
 | Will not allow maximum harvest of solar | 
 | Power derating | 
| 
 | 
 | 
 | energy | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | > 600 | 
 | Will shut down and may cause damage to the | 
 | Shutdown | 
| 
 | 
 | 
 | inverter; stops selling surplus energy | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| Voltage | The maximum power point voltage of a string connected to the GT Inverter should | ||||
| requirements | be a minimum of 195 Vdc. If it is less than 195 Vdc, then the power point is | ||||
| 
 | shifted and the PV voltage is regulated to 195 Vdc. | 
 | 
 | ||
| 
 | By regulating the operating voltage of the solar modules, the MPPT software | ||||
| 
 | maximizes their output energy. | 
 | 
 | ||
| 
 | Effects of array voltages outside of the MPPT operational window are shown in | ||||
| 
 | Table  | 
 | 
 | 
 | 
 | 
| Maximum PV | The solar array should be sized such that its maximum power output does not | ||||
| Power | exceed the limits of the MPPT operational window (195 to 550 Vdc). See | ||||
| 
 | “Guidelines for Matching PV Array Size to Xantrex Grid Tie Solar Inverter | ||||
| 
 | Input”. | 
 | 
 | 
 | 
 | 
Under no conditions should the array voltage exceed 600 VOC (open circuit voltage).