Electrical Specifications
Adjustable Disconnect Settings
The adjustable disconnect setting values vary depending on whether the inverter is a 208 Vac/60 Hz, 240 Vac/60 Hz, or 230 Vac/50 Hz model. Utility permission is required prior to changing the settings on the inverter.
The default values of these settings differ from the utility specifications on page
|
| Default Values |
| Adjustment Range |
| ||
Setting |
|
|
|
|
|
| |
208 Vac/60 Hz | 240 Vac/60 Hz | 230 Vac/50 Hz | From... | To... | Accuracy | ||
|
|
|
|
|
|
| |
AC Low Voltage | 186 Vac | 214 Vac | 205 Vac | 180 Vac | 269 Vac | +/– 3 Vac | |
|
|
|
| ||||
AC High Voltage | 225 Vac | 261 Vac | 250 Vac | ||||
|
|
| |||||
|
|
|
|
|
|
| |
AC Low Frequency | 59.4 Hz | 47.1 Hz | 46.0 Hz | 62.0 Hz | +/– 0.1 Hz | ||
|
|
|
| ||||
AC High Frequency | 60.4 Hz | 50.9 Hz | |||||
|
|
| |||||
|
|
|
|
|
|
| |
Reconnect Delay |
| 305 sec. |
| 60 sec. | 600 sec. | +/– 5 sec. | |
|
|
|
|
|
|
|
Output Power Versus Ambient Temperature
Once the heat sink on the inverter reaches a maximum temperature limit, the GT Inverter reduces its energy output to ensure maximum component ratings are not exceeded.
GT3.0 GRID TIE SOLAR INVERTER
Output Power versus Ambient Temperature
| 3500 |
|
|
|
|
|
|
|
|
|
| 3000 |
|
|
|
|
|
|
|
|
|
| 2500 |
|
|
|
|
|
|
|
|
|
(Watts) | 2000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Power | 1500 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 1000 |
|
|
|
|
|
|
|
|
|
| 500 |
|
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
|
| 5 | 15 | 25 | 35 | 45 | 55 | 65 |
Ambient Temperature (C)
Standard Unit
w/ Optional Fan Kit