Wiring the Inverter

Connecting Inverters in Parallel

GT Inverters can be connected in a parallel configuration for larger PV array systems. In this configuration, separate solar arrays are required for each GT Inverter unit. The output of each GT Inverter feeds a separate dual-pole 20-Amp circuit breaker (L1 and L2) in the main utility service panel.

DC and AC Wiring for Inverters in Parallel

Connecting DC wiring

Connecting AC wiring

The following procedures are illustrated in Figure 3-6. The illustration and instructions assume only two inverters, but in fact more than two inverters can be used in a parallel configuration.

If there will be more than one PV string, label the positive and negative wire pairs appropriately (for example: PV 1, PV 2).

To wire the PV array to GT Inverters in parallel:

1.Install the DC conduit from the PV strings to the GT Inverter wiring boxes, through appropriate knockout holes. Metal conduit is highly recommended.

2.Remove the wiring box cover (see page 3–2).

3.Route the wires from the PV string(s) through the conduit and into the wiring box.

4.Connect the DC Ground from each PV array to the GND bar in the wiring box.

5.Follow the instructions on page 3–4 for connecting POSITIVE (+) and NEGATIVE (–) wires from each PV array to each GT Inverter.

6.Ensure all connections are correctly wired and properly torqued according to values shown in Table 3-1 on page 3–5.

To wire the main utility service panel to the GT Inverters in parallel:

1.Run conduit from the main utility service panel to the wiring boxes of the GT Inverters.

2.Follow the instructions on page 3–7 for connecting L1 and L2 HOT wires and ground wire from the main utility service panel to each GT Inverter.

3.Ensure all connections are correctly wired and properly torqued according to values shown in Table 3-1 on page 3–5.

3–10

975-0131-01-01

Page 64
Image 64
Xantrex Technology GT3.0 owner manual Connecting Inverters in Parallel, DC and AC Wiring for Inverters in Parallel