Liebert 130 kVA user manual Cable rating, General Notes, Cable Connections, Safety earth

Page 34

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

3.1.2Cable rating

 

 

 

 

 

 

NOMINAL CURRENT (Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS

3 Phase Input Mains with full

 

 

 

 

Battery at minimum

 

Rating

 

battery re-charge

 

1 Phase Output at full load

 

 

 

 

 

 

Battery Voltage

 

(kVA)

(less 5% for 12 pulse)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380V

 

400V

 

415V

110V

115V

120V

 

380V

 

400V

 

415V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

63

 

60

 

58

272

260

250

 

83

 

80

 

77.5

40

84

 

80

 

77

364

349

334

 

110

 

106

 

103

50

105

 

100

 

96

454

434

416

 

137

 

133

 

129

60

126

 

119

 

115

545

521

500

 

164

 

159

 

155

80

165

 

157

 

151

727

695

666

 

219

 

213

 

206

120

245

 

233

 

223

1090

1043

1000

 

329

 

319

 

310

130

259

 

247

 

238

1181

1130

1083

 

357

 

346

 

336

150

300

 

285

 

275

1363

1304

1250

 

412

 

399

 

387

Table 3-1 UPS Module cabinet power cable rating

3.1.3General Notes

The following are guidelines only and superseded by local regulations and codes of practice where applicable:

1.The neutral conductor should be sized same as the output/ bypass current.

2.The earth conductor should be sized for carrying fault current for atleast 3 to 5 seconds or as guided by local electrical rules.

3.Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably.

4.When sizing battery cables, a maximum volt drop of 3V d.c. is permissible at the current ratings given in Table 3-1.

3.1.4Cable Connections

The rectifier input, bypass, output and battery power cables (all require lug type terminations) and are connected to busbars situated below the power isolator switches - as shown in figure 3.1 for 80kVA and fig 3.2 for 120 /160/ 200kVA.

A terminal block X3 is used for connecting the control cables to the battery circuit breaker and a second terminal block X4 is used for the external emergency stop facility, external OFF inverter, ext. Bypass, etc. these are female spade type connections (Fast-on 6.3 x 0.8) and are described later in Section 3.2

3.1.5Safety earth

The safety earth busbar is located between the Bypass and Output power supply connections as shown in the figure 3.1. The safety earth cable must be connected to the earth busbar and bonded to each cabinet in the system.

All cabinets and cable trunking should be earthed in accordance with local regulations.

14

Image 34
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Design Concept Single Module block diagramIntroduction Hipulse Module DesignUPS Power switches configuration Bypass SuppliesUPS Module fault Return of power mainsOff-Battery Normal OperationMaintenance Bypass OverloadBattery temperature compensation UPS Power Switch ConfigurationBattery circuit breaker System ExpansionHipulse Single Phase ‘1+N’ UPS System Installation Procedure Environmental considerations Battery locationUPS location Mechanical Considerations Installation Drawings Preliminary ChecksOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Battery cables Power CablingSystem Configuration Module input cablesGeneral Notes Safety earthCable rating Cable ConnectionsProtective devices Protection against earth faults RCD devicesSplit Bypass Parallel 1+N UPS BatteryCabling procedure Input ConnectionsInput-module Parallel Connections Auxiliary Connections+VE -VE Cable connections for 130 kVA 1Ph UPSControl cables Battery ControlAuxiliary Terminal Block detail Auxiliary Terminal Block X3 and X4 at UPS DescriptionEmergency Stop Battery ConnectionBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System Operator Control and Display Panel UPS Operator Control / Display PanelOperator control panel Inverter control switchSingle module operator control panel Mimic indicationsMenu Control switches Operator Panel and LCD DisplayOutput Parameters Bargraph SelectionEPO on UPS module Menu OptionsMap of screen display available to operator Or. for Instanc eInfo Window Default WindowLCD Display Panel Messages Initializing Window Main Menu WindowOption Selection Mode Alarm / Warning MessagesShutdown General notes Power SwitchesOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Your load is now powered via the Static Bypass system Normal OperationYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Language Selection Changing the current Date and TimeHipulse Single Phase ‘1+N’ UPS System Battery Installation SafetyUPS Batteries Temperature considerations Battery populationConnecting the Battery Battery protectionBattery Racks IntroductionBattery Supply To UPS Cabinet Battery Installation Battery circuit breakerBattery Control and Power Connections Battery temperature Board Display Panel Interpretation LED InterpretationProcedure to carry out the reset see Operating Instructions Sr. No Display Message Alarm Interpretation Display Panel MessagesBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System + N System General1+N System block diagram with Separate Batteries BatteryConnection of 1+N system parallel single bus cables Installation procedureInter-module control Connection of EPO Push Button System Start-up and shutdown procedures Separate Batteries Operating InstructionDefault window Hipulse Single Phase ‘1+N’ UPS System Display Panel message interpretation in 1+N System Complete system shutdownConformity and Standard UPS Mechanical CharacteristicsUPS Environmental UPS Electrical Characteristics C T I F I E R I N P U T M a I N SUPS Electrical Characteristics DC Intermediate Circuit Rated Power KVA 130UPS Electrical Characteristics Inverter Output V E R T E R O U T P U TUPS Electrical Characteristics Bypass Input Mains Protection, bypass lineHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Remote Alarm Monitor RAM ConnectionsUPS 220/240V AC 50 HzIndication & Metering TerminationProtection Bypass Isolation Cubicle