User Manual
Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
|
| At this point the UPS inverter stops but the load |
|
| continues to be supplied by the bypass mains. |
|
| The Load on Mains indicator light (6) on the unit's |
|
| synoptic panel flashes yellow, and the Load on |
|
| Inverter indicator light (5) goes off. |
|
|
|
|
| Your load is now powered via the Static Bypass system |
|
|
|
|
| 5. Unfasten the lock, release the internal safety bar |
|
| and close the maintenance bypass power switch |
|
| Q3. Open the Rectifier input power switch Q1, the |
|
| Output power switch Q4, the bypass power switch |
|
| Q2 and the Battery circuit breaker. This is located |
|
| inside the battery cabinet (if used) or is otherwise |
|
| located adjacent to the battery racks. The unit will |
|
| power down but the load will continue to be |
|
| supplied by the manual bypass. |
|
|
|
|
| WARNING |
|
|
|
|
| Wait 5 minutes for the internal D.C. busbar capacitors |
|
| to discharge. |
|
|
|
|
WARNING
The following points will be live within the UPS:
-Bypass a.c. input supply terminals.
-Maintenance Bypass power switch.
-Static Bypass power switch.
-UPS output terminals.
Input and Output terminals remain protected by a metallic cover.
Your load is now powered from the maintenance bypass
system and the UPS is completely shut down.
37