Liebert 130 kVA user manual Shutdown, On Static Bypass, General notes Power Switches

Page 51

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

CHAPTER 5

Operating Instructions

5.1Introduction

The UPS can be considered to be in one of three operating conditions:

Normal operation

All relevant power switches and circuit breakers closed, the load is powered by the UPS.

Shutdown

All power switches and circuit breakers open - no load power.

On Static Bypass

The load power is supplied through the mains static bypass line. This may be considered as an intermediate operating condition being utilized for the purpose of load transfers between inverter and maintenance bypass or supply under abnormal operating conditions.

ECOMODE

All the relevant power supply switches and the battery switch are off, and the load is fed by the Bypass Mains through the UPS Static Transfer Switch, while the Inverter remains on stand-by.

This chapter contains instructions which enable you to switch between the three above conditions, to carry out a RESET after a fault transfer and how to switch OFF the inverter.

5.1.1General notes

Note1: All the user controls and indicators mentioned in these procedures are identified in chapter 1. Some of diagrams are repeated here to assist in understanding the procedures.

Note2: The audible alarm may annunciate at various points in these procedures. It can be cancelled at any time by pressing the ‘Alarm Reset’ push-button.

Note3: The Hipulse UPS System incorporates an optional automatic boost charge facility which can be used in systems containing conventional flooded lead-acid batteries. If this type of battery is used in your installation you may notice that the battery charger voltage may be greater than its nominal (432V d.c. for 380V a.c., 446V d.c. for 400V a.c. and 459V d.c. for 415V a.c. system) when the mains supply returns from a prolonged outage. This is the normal response of the boost charge facility; the charger voltage should return to normal after a few hours.

5.1.2Power Switches

The UPS can be separated by means of power switches, mounted inside the cabinet and accessible after opening the front door, which has a key.

The location of the UPS power switches is shown in Figure 5-1. The UPS module power switches are:

oQ1 - Input MCCB: connects the UPS with he mains supply.

oQ2 - Bypass Isolator: connects the UPS with the bypass supply.

oQ3 - Maintenance Bypass Isolator (Padlocked) permits supply of the load directly by the bypass line for maintenance of the UPS module.

The internal maintenance bypass must not be used when the UPS system is comprised of more

than two UPS modules in parallel.

oQ4 - Output Isolator: connects the output of the UPS to the load.

Note: The battery interrupter is not expected inside of the UPS and should be installed in the proximity of the respective battery bank.

31

Image 51
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Hipulse Module Design Single Module block diagramIntroduction Design ConceptBypass Supplies UPS Power switches configurationNormal Operation Return of power mainsOff-Battery UPS Module faultOverload Maintenance BypassSystem Expansion UPS Power Switch ConfigurationBattery circuit breaker Battery temperature compensationHipulse Single Phase ‘1+N’ UPS System Installation Procedure Battery location Environmental considerationsUPS location Mechanical Considerations Preliminary Checks Installation DrawingsOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Module input cables Power CablingSystem Configuration Battery cablesCable Connections Safety earthCable rating General NotesProtection against earth faults RCD devices Protective devicesSplit Bypass Input Connections UPS BatteryCabling procedure Parallel 1+NAuxiliary Connections Input-module Parallel ConnectionsCable connections for 130 kVA 1Ph UPS +VE -VEBattery Control Control cablesAuxiliary Terminal Block detail Description Auxiliary Terminal Block X3 and X4 at UPSBattery Connection Emergency StopBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System UPS Operator Control / Display Panel Operator Control and Display PanelMimic indications Inverter control switchSingle module operator control panel Operator control panelOperator Panel and LCD Display Menu Control switchesBargraph Selection Output ParametersMenu Options EPO on UPS moduleOr. for Instanc e Map of screen display available to operatorMain Menu Window Default WindowLCD Display Panel Messages Initializing Window Info WindowAlarm / Warning Messages Option Selection ModeGeneral notes Power Switches ShutdownOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Normal Operation Your load is now powered via the Static Bypass systemYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Changing the current Date and Time Language SelectionHipulse Single Phase ‘1+N’ UPS System Safety Battery InstallationUPS Batteries Battery population Temperature considerationsIntroduction Battery protectionBattery Racks Connecting the BatteryBattery Supply To UPS Cabinet Battery circuit breaker Battery InstallationBattery Control and Power Connections Battery temperature Board LED Interpretation Display Panel InterpretationProcedure to carry out the reset see Operating Instructions Display Panel Messages Sr. No Display Message Alarm InterpretationBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System General + N SystemBattery 1+N System block diagram with Separate BatteriesInstallation procedure Connection of 1+N system parallel single bus cablesInter-module control Connection of EPO Push Button Operating Instruction System Start-up and shutdown procedures Separate BatteriesDefault window Hipulse Single Phase ‘1+N’ UPS System Complete system shutdown Display Panel message interpretation in 1+N SystemUPS Mechanical Characteristics Conformity and StandardUPS Environmental C T I F I E R I N P U T M a I N S UPS Electrical CharacteristicsRated Power KVA 130 UPS Electrical Characteristics DC Intermediate CircuitV E R T E R O U T P U T UPS Electrical Characteristics Inverter OutputProtection, bypass line UPS Electrical Characteristics Bypass Input MainsHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System RAM Connections Remote Alarm Monitor220/240V AC 50 Hz UPSTermination Indication & MeteringProtection Bypass Isolation Cubicle