Liebert 130 kVA Installation procedure, Connection of 1+N system parallel single bus cables

Page 85

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

8.2Installation procedure

8.2.1Preliminary Checks

Be sure that a parallel kit is present and fitted in each of the modules, and that the modules are of the same rating and with the same software and hardware release (see section 4.1.2 – Info window)

WARNING

Fitting of the parallel kits and board setting required to convert from Single Module to 1+N must be made by qualified and trained personnel. This operation involves also setting of system with separate batteries or common batteries.

8.2.2Protective Devices

Refer to the instructions supplied in Chapter 3 – Electrical Installation - Section 3.1.6.

8.2.3Power Cables

Input Bypass and Rectifier, outputs of module as described in Chapter 3.

8.2.4Control Cables

Inter-module control

Modules are connected as shown in figure 8-3 using connected the other via Parallel Connector Board with shielded 34-way cables.

These cables are connected between the ‘N’ modules to pass control signals which govern module synchronization, load sharing, battery charge current sharing (in a common battery installation), load transfer operation and other general control and alarm functions. These signals are necessary to ensure correct system operation, and built-in redundancy allows the system to function if ever one of the ‘N’ cables becomes disconnected.

Cables entry is as identified in the mechanical drawings in Chapter 2.

UPS Module 1

To Parallel PCB

X3

Parallel

Connect.

Board

X1

X2

UPS Module 2

To Parallel PCB

X3

Parallel

Connect.

Board

X1

X2

UPS Module 3

To Parallel PCB

X3

Parallel

Connect.

Board

X1

X2

UPS Module 4

To Parallel PCB

X3

Parallel

Connect.

Board

X1

X2

UPS Module 5

To Parallel PCB

X3

Parallel

Connect.

Board

X1

X2

UPS Module 6

To Parallel PCB

X3

Parallel

Connect.

Board

X1

X2

Fig 8-2: Connection of '1+N' system parallel single bus cables

65

Image 85
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Introduction Single Module block diagramDesign Concept Hipulse Module DesignBypass Supplies UPS Power switches configurationOff-Battery Return of power mainsUPS Module fault Normal OperationOverload Maintenance BypassBattery circuit breaker UPS Power Switch ConfigurationBattery temperature compensation System ExpansionHipulse Single Phase ‘1+N’ UPS System Installation Procedure Environmental considerations Battery locationUPS location Mechanical Considerations Preliminary Checks Installation DrawingsOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details System Configuration Power CablingBattery cables Module input cablesCable rating Safety earthGeneral Notes Cable ConnectionsProtective devices Protection against earth faults RCD devicesSplit Bypass Cabling procedure UPS BatteryParallel 1+N Input ConnectionsAuxiliary Connections Input-module Parallel ConnectionsCable connections for 130 kVA 1Ph UPS +VE -VEControl cables Battery ControlAuxiliary Terminal Block detail Description Auxiliary Terminal Block X3 and X4 at UPSEmergency Stop Battery ConnectionBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System UPS Operator Control / Display Panel Operator Control and Display PanelSingle module operator control panel Inverter control switchOperator control panel Mimic indicationsOperator Panel and LCD Display Menu Control switchesBargraph Selection Output ParametersMenu Options EPO on UPS moduleOr. for Instanc e Map of screen display available to operatorLCD Display Panel Messages Initializing Window Default WindowInfo Window Main Menu WindowAlarm / Warning Messages Option Selection ModeShutdown General notes Power SwitchesOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Normal Operation Your load is now powered via the Static Bypass systemYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Changing the current Date and Time Language SelectionHipulse Single Phase ‘1+N’ UPS System Safety Battery InstallationUPS Batteries Battery population Temperature considerationsBattery Racks Battery protectionConnecting the Battery IntroductionBattery Supply To UPS Cabinet Battery circuit breaker Battery InstallationBattery Control and Power Connections Battery temperature Board LED Interpretation Display Panel InterpretationProcedure to carry out the reset see Operating Instructions Display Panel Messages Sr. No Display Message Alarm InterpretationBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System General + N SystemBattery 1+N System block diagram with Separate BatteriesConnection of 1+N system parallel single bus cables Installation procedureInter-module control Connection of EPO Push Button Operating Instruction System Start-up and shutdown procedures Separate BatteriesDefault window Hipulse Single Phase ‘1+N’ UPS System Complete system shutdown Display Panel message interpretation in 1+N SystemConformity and Standard UPS Mechanical CharacteristicsUPS Environmental C T I F I E R I N P U T M a I N S UPS Electrical CharacteristicsRated Power KVA 130 UPS Electrical Characteristics DC Intermediate CircuitV E R T E R O U T P U T UPS Electrical Characteristics Inverter OutputProtection, bypass line UPS Electrical Characteristics Bypass Input MainsHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System RAM Connections Remote Alarm Monitor220/240V AC 50 Hz UPSIndication & Metering TerminationProtection Bypass Isolation Cubicle