Liebert 130 kVA user manual Ecomode

Page 55

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

>MEASUREMENT < FUNCTION MAINTENANCE

SETUP

OUTPUT

INPUT

>BATTERY<

TEMPERATURE

Select MEASUREMENT and press ENTER key.

Select BATTERY and d.c. busbar voltage will be displayed:

BATTERY

 

 

VOLTAGE

446

[V]

CURRENT

001

[A]

CHARGE

000

[%]

 

 

 

If the voltage indicated is satisfactory (432V d.c. for 380V a.c. system, 446VV d.c. for 400V a.c. system and 459V d.c. for a 415V a.c. system) press the Escape key repeatedly until the display returns to the original window.

6.Manually close the battery circuit breaker. This is located inside the battery cabinet (if used) or is otherwise located adjacent to the battery racks.

The Module Mimic indicator (3) Battery unavailable should extinguish. Several LED’s on the Battery state of charge bargraph (17) will illuminate showing the battery state of charge

When the battery circuit breaker has been closed and the inverter has stabilized the screen will change to the default window.

NORMAL OPERATION

hh.mm.ss dd.mm.yy

Default window:

The message shown below, will be seen on the default screen whenever the UPS is operating normally:

The top lines display the UPS operational status and indicates alarm conditions when they occur; and line four normally shows the time and date.

NORMAL OPERATION (ECOMODE)

hh.mm.ss dd.mm.yy

The UPS is operating normally with its

Inverter supplying the load.

ECOMODE:

The following message will appear in the default screen whenever the UPS is operating in ECOMODE. The load is supplied through Bypass Mains.

The UPS is operating in ECOMODE with the Bypass

Mains supplying the load.

35

Image 55
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Hipulse Module Design Single Module block diagramIntroduction Design ConceptBypass Supplies UPS Power switches configurationNormal Operation Return of power mainsOff-Battery UPS Module faultOverload Maintenance BypassSystem Expansion UPS Power Switch ConfigurationBattery circuit breaker Battery temperature compensationHipulse Single Phase ‘1+N’ UPS System Installation Procedure Environmental considerations Battery locationUPS location Mechanical Considerations Preliminary Checks Installation DrawingsOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Module input cables Power CablingSystem Configuration Battery cablesCable Connections Safety earthCable rating General NotesProtective devices Protection against earth faults RCD devicesSplit Bypass Input Connections UPS BatteryCabling procedure Parallel 1+NAuxiliary Connections Input-module Parallel ConnectionsCable connections for 130 kVA 1Ph UPS +VE -VEControl cables Battery ControlAuxiliary Terminal Block detail Description Auxiliary Terminal Block X3 and X4 at UPSEmergency Stop Battery ConnectionBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System UPS Operator Control / Display Panel Operator Control and Display PanelMimic indications Inverter control switchSingle module operator control panel Operator control panelOperator Panel and LCD Display Menu Control switchesBargraph Selection Output ParametersMenu Options EPO on UPS moduleOr. for Instanc e Map of screen display available to operatorMain Menu Window Default WindowLCD Display Panel Messages Initializing Window Info WindowAlarm / Warning Messages Option Selection ModeShutdown General notes Power SwitchesOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Normal Operation Your load is now powered via the Static Bypass systemYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Changing the current Date and Time Language SelectionHipulse Single Phase ‘1+N’ UPS System Safety Battery InstallationUPS Batteries Battery population Temperature considerationsIntroduction Battery protectionBattery Racks Connecting the BatteryBattery Supply To UPS Cabinet Battery circuit breaker Battery InstallationBattery Control and Power Connections Battery temperature Board LED Interpretation Display Panel InterpretationProcedure to carry out the reset see Operating Instructions Display Panel Messages Sr. No Display Message Alarm InterpretationBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System General + N SystemBattery 1+N System block diagram with Separate BatteriesConnection of 1+N system parallel single bus cables Installation procedureInter-module control Connection of EPO Push Button Operating Instruction System Start-up and shutdown procedures Separate BatteriesDefault window Hipulse Single Phase ‘1+N’ UPS System Complete system shutdown Display Panel message interpretation in 1+N SystemConformity and Standard UPS Mechanical CharacteristicsUPS Environmental C T I F I E R I N P U T M a I N S UPS Electrical CharacteristicsRated Power KVA 130 UPS Electrical Characteristics DC Intermediate CircuitV E R T E R O U T P U T UPS Electrical Characteristics Inverter OutputProtection, bypass line UPS Electrical Characteristics Bypass Input MainsHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System RAM Connections Remote Alarm Monitor220/240V AC 50 Hz UPSIndication & Metering TerminationProtection Bypass Isolation Cubicle