User Manual
Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
>MEASUREMENT < FUNCTION MAINTENANCE
SETUP
OUTPUT
INPUT
>BATTERY<
TEMPERATURE
Select MEASUREMENT and press ENTER key.
Select BATTERY and d.c. busbar voltage will be displayed:
BATTERY |
|
|
VOLTAGE | 446 | [V] |
CURRENT | 001 | [A] |
CHARGE | 000 | [%] |
|
|
|
If the voltage indicated is satisfactory (432V d.c. for 380V a.c. system, 446VV d.c. for 400V a.c. system and 459V d.c. for a 415V a.c. system) press the Escape key repeatedly until the display returns to the original window.
6.Manually close the battery circuit breaker. This is located inside the battery cabinet (if used) or is otherwise located adjacent to the battery racks.
The Module Mimic indicator (3) Battery unavailable should extinguish. Several LED’s on the Battery state of charge bargraph (17) will illuminate showing the battery state of charge
When the battery circuit breaker has been closed and the inverter has stabilized the screen will change to the default window.
NORMAL OPERATION
hh.mm.ss dd.mm.yy
Default window:
The message shown below, will be seen on the default screen whenever the UPS is operating normally:
The top lines display the UPS operational status and indicates alarm conditions when they occur; and line four normally shows the time and date.
NORMAL OPERATION (ECOMODE)
hh.mm.ss dd.mm.yy
The UPS is operating normally with its
Inverter supplying the load.
ECOMODE:
The following message will appear in the default screen whenever the UPS is operating in ECOMODE. The load is supplied through Bypass Mains.
The UPS is operating in ECOMODE with the Bypass
Mains supplying the load.
35