Liebert 130 kVA user manual Procedure to carry out the reset see Operating Instructions

Page 76

User Manual

 

Hipulse - Single Phase ‘1+N’ UPS System

 

130 kVA - 110V

 

 

 

1.

If [OVERTEMPERATURE] or [OVERLOAD] alarm messages are active then (after allowing

the

 

 

 

 

UPS to cool / checking that the load current on the Bypass line is not excessive) use the

 

 

 

 

procedure to carry out the reset (see Chapter 5 – Operating Instructions).

 

 

 

2.

Check that the conditions for led(2) are satisfied.

 

 

 

3.

Check that the Inverter led(8)- yellow – is OFF, otherwise follow Inverter switch ON procedure.

 

 

 

4.

Check that no conditions exist which will prevent switching the INV ON (e.g. PC command).

 

 

 

5.

Verify that condition leading to an emergency stop has not happened, in which case a Reset

 

 

 

 

must be carried out.

 

 

 

5.

ON

If this green led is OFF, then it signifies that the load has been transferred to the Static bypass supply. If

 

 

 

this is an automatic change over it will be accompanied by a fault warning on the display panel. Take the

 

 

 

appropriate actions for the display indication (see Display alarm message table 7-2).

 

6.

OFF

This led is mutually exclusive to led(5).

If this amber led is ON, the load has been transferred to the

 

 

 

Bypass mains supply. Verify the cause by following the alarm indications at the LCD display panel. If the

 

 

 

above checks prove unsatisfactory then seek qualified assistance.

 

13.

OFF

This red led will flash ON and OFF and indicates that the UPS has detected fault, it will be accompanied by

 

 

 

a message on the display panel, take the required actions for the display panel message (see Display

 

 

 

alarm message table 7-2). This will be accompanied by an audible warning. Pressing the Alarm silence

 

 

 

switch (14) stops the audible alarm, but leaves the warning message displayed until the appropriate

 

 

 

condition is rectified.

 

 

 

16.

OFF

If this yellow led is ON it signifies that the battery voltage is low and that the end of battery discharge is

 

 

 

near. This will be accompanied by audible warning.

 

17.

N/A

This is a bargraph indicating the battery charge state and would normally have four or five of the leds ON.

 

 

 

When the unit runs on battery, this bargraph changes to give an indication of the time remaining on the

 

 

 

battery.

 

 

 

 

18.

N/A

This is a bargraph indicating the % of the total load that is being applied to the system.

 

 

 

 

 

19.

OFF

If this yellow led is ON it signifies that

the applied load has exceeded the maximum. It will be

 

 

 

accompanied by all five load bargraph leds being ON (item 18), the Alarm warning indication flashing RED

 

 

 

(item 13) and an OVERLOAD messages on the visual display. This will be accompanied by an audible

 

 

 

warning. Reduce the load immediately.

 

 

56

Image 76
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Single Module block diagram IntroductionDesign Concept Hipulse Module DesignUPS Power switches configuration Bypass SuppliesReturn of power mains Off-BatteryUPS Module fault Normal OperationMaintenance Bypass OverloadUPS Power Switch Configuration Battery circuit breakerBattery temperature compensation System ExpansionHipulse Single Phase ‘1+N’ UPS System Installation Procedure Environmental considerations Battery locationUPS location Mechanical Considerations Installation Drawings Preliminary ChecksOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Power Cabling System ConfigurationBattery cables Module input cablesSafety earth Cable ratingGeneral Notes Cable ConnectionsProtective devices Protection against earth faults RCD devicesSplit Bypass UPS Battery Cabling procedureParallel 1+N Input ConnectionsInput-module Parallel Connections Auxiliary Connections+VE -VE Cable connections for 130 kVA 1Ph UPSControl cables Battery ControlAuxiliary Terminal Block detail Auxiliary Terminal Block X3 and X4 at UPS DescriptionEmergency Stop Battery ConnectionBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System Operator Control and Display Panel UPS Operator Control / Display PanelInverter control switch Single module operator control panelOperator control panel Mimic indicationsMenu Control switches Operator Panel and LCD DisplayOutput Parameters Bargraph SelectionEPO on UPS module Menu OptionsMap of screen display available to operator Or. for Instanc eDefault Window LCD Display Panel Messages Initializing WindowInfo Window Main Menu WindowOption Selection Mode Alarm / Warning MessagesShutdown General notes Power SwitchesOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Your load is now powered via the Static Bypass system Normal OperationYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Language Selection Changing the current Date and TimeHipulse Single Phase ‘1+N’ UPS System Battery Installation SafetyUPS Batteries Temperature considerations Battery populationBattery protection Battery RacksConnecting the Battery IntroductionBattery Supply To UPS Cabinet Battery Installation Battery circuit breaker Battery Control and Power Connections Battery temperature Board Display Panel Interpretation LED InterpretationProcedure to carry out the reset see Operating Instructions Sr. No Display Message Alarm Interpretation Display Panel MessagesBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System + N System General1+N System block diagram with Separate Batteries BatteryConnection of 1+N system parallel single bus cables Installation procedureInter-module control Connection of EPO Push Button System Start-up and shutdown procedures Separate Batteries Operating InstructionDefault window Hipulse Single Phase ‘1+N’ UPS System Display Panel message interpretation in 1+N System Complete system shutdownConformity and Standard UPS Mechanical CharacteristicsUPS Environmental UPS Electrical Characteristics C T I F I E R I N P U T M a I N SUPS Electrical Characteristics DC Intermediate Circuit Rated Power KVA 130UPS Electrical Characteristics Inverter Output V E R T E R O U T P U TUPS Electrical Characteristics Bypass Input Mains Protection, bypass lineHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Remote Alarm Monitor RAM ConnectionsUPS 220/240V AC 50 HzIndication & Metering TerminationProtection Bypass Isolation Cubicle