Liebert 130 kVA user manual BYP. Absent

Page 79

User Manual

 

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

14.

BATTERY: E.O.D.

Battery discharge has continued beyond a preset value. The

 

 

 

inverter will shut down, the system will attempt a transfer to bypass.

 

 

 

If Bypass is not available, any load connected to the UPS will be

 

 

 

without power.

 

 

 

 

15.

RECT. OFF

The RECT. OFF alarm is active whenever the battery charger

 

 

 

(rectifier) is not producing its correct output voltage. This can be

caused by an operator selection to OFF, an Input supply failure, an open rectifier a.c. input power switch or an internal fault which may be accompanied by one of the fault conditions.

16.RECT. SWITCH OPEN RECT. CURRENT LIMIT BATTERY: FUSE FAIL DC BUS: FAST OVERVOL

Most of the rectifier fault messages are self explanatory however, the DC BUS: FAST OVERVOLTAGE message informs the operator the d.c. busbar voltage is too high.

17.

BYP. ABSENT

INPUT FAILURE: input a.c. supply failed or out of specified

 

BYP. OVERVOLTAGE

acceptable range. Do not switch OFF the inverter while this

 

BYP. UNDERVOLTAGE

indication is active or the load will lose its power.

 

BYP. FREQUENCY ERROR

 

 

 

 

18.

BYP. SCR FAILURE

One or more of the static switch SCR’s has developed a fault. The

 

 

bypass would not support the load in the event of a UPS failure,

 

 

immediate action is required. Seek qualified assistance.

 

 

 

19.

BYP. PHASE ROT. ERROR

This message informs the operator that the input power lines have

 

 

been cross-connected and the phases sequence is incorrect.

 

 

 

20.

MANUAL BYPASS CLOSED

This is a status warning that the load is being powered through the

 

 

maintenance bypass line and is unprotected from mains supply

 

 

aberrations.

 

 

 

21.

INV. UNSYNCHRONIZED

This warns that the inverter is not synchronized with the bypass

 

 

supply, which is normally due to a problem with the bypass supply

 

 

being outside an acceptable frequency window. Do not switch OFF

 

 

the inverter when this alarm is active or the load will experience a

 

 

200 millisecond power break.

 

 

 

59

Image 79
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Hipulse Module Design Single Module block diagramIntroduction Design ConceptBypass Supplies UPS Power switches configurationNormal Operation Return of power mainsOff-Battery UPS Module faultOverload Maintenance BypassSystem Expansion UPS Power Switch ConfigurationBattery circuit breaker Battery temperature compensationHipulse Single Phase ‘1+N’ UPS System Installation Procedure Environmental considerations Battery locationUPS location Mechanical Considerations Preliminary Checks Installation DrawingsOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Module input cables Power CablingSystem Configuration Battery cablesCable Connections Safety earthCable rating General NotesProtective devices Protection against earth faults RCD devicesSplit Bypass Input Connections UPS BatteryCabling procedure Parallel 1+NAuxiliary Connections Input-module Parallel ConnectionsCable connections for 130 kVA 1Ph UPS +VE -VEControl cables Battery ControlAuxiliary Terminal Block detail Description Auxiliary Terminal Block X3 and X4 at UPSEmergency Stop Battery ConnectionBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System UPS Operator Control / Display Panel Operator Control and Display PanelMimic indications Inverter control switchSingle module operator control panel Operator control panelOperator Panel and LCD Display Menu Control switchesBargraph Selection Output ParametersMenu Options EPO on UPS moduleOr. for Instanc e Map of screen display available to operatorMain Menu Window Default WindowLCD Display Panel Messages Initializing Window Info WindowAlarm / Warning Messages Option Selection ModeShutdown General notes Power SwitchesOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Normal Operation Your load is now powered via the Static Bypass systemYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Changing the current Date and Time Language SelectionHipulse Single Phase ‘1+N’ UPS System Safety Battery InstallationUPS Batteries Battery population Temperature considerationsIntroduction Battery protectionBattery Racks Connecting the BatteryBattery Supply To UPS Cabinet Battery circuit breaker Battery InstallationBattery Control and Power Connections Battery temperature Board LED Interpretation Display Panel Interpretation Procedure to carry out the reset see Operating Instructions Display Panel Messages Sr. No Display Message Alarm InterpretationBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System General + N SystemBattery 1+N System block diagram with Separate BatteriesConnection of 1+N system parallel single bus cables Installation procedureInter-module control Connection of EPO Push Button Operating Instruction System Start-up and shutdown procedures Separate BatteriesDefault window Hipulse Single Phase ‘1+N’ UPS System Complete system shutdown Display Panel message interpretation in 1+N SystemConformity and Standard UPS Mechanical CharacteristicsUPS Environmental C T I F I E R I N P U T M a I N S UPS Electrical CharacteristicsRated Power KVA 130 UPS Electrical Characteristics DC Intermediate CircuitV E R T E R O U T P U T UPS Electrical Characteristics Inverter OutputProtection, bypass line UPS Electrical Characteristics Bypass Input MainsHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System RAM Connections Remote Alarm Monitor220/240V AC 50 Hz UPSIndication & Metering TerminationProtection Bypass Isolation Cubicle