Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
overload present.
7. | OVERLOAD SHUTDOWN | This message informs the operator that the load has been |
|
| transferred to bypass due to an inverter overload. |
|
|
|
8. | OUTPUT SWITCH OPEN | This is a status alarm. The output switch must be selected |
|
| ‘CLOSED’ at all times except when operating on the Maintenance |
|
| bypass supply. |
|
|
|
9. | BYPASS SWITCH OPEN | This is a status alarm. The bypass input switch must be closed all |
|
| the times. |
|
|
|
10. | BATTERY C.B. OPEN | This is a status indication only. Note that if the UPS is operating |
|
| with the Battery circuit breaker open, and the mains power fails, |
|
| then the UPS output will also fail together with load power, since |
|
| the inverter has no battery backup. |
|
|
|
11. | BATTERY: FUSE FAIL | This problem should be rectified as soon as possible. If the mains |
|
| power fails then the UPS output will also fail together with load |
|
| power, since there is no battery backup. |
|
|
|
12. | BATTERY: TEST FAILED | The system has carried out a test of the battery. If this alarm is not |
|
| accompanied by a [BATTERY C.B. OPEN] or [BATTERY: FUSE FAIL] |
|
| message then a full check of the Battery bank is required. |
|
|
|
13. | DC BUS: UNDERVOLTAGE | When the inverter is operating on the battery this message is |
|
| displayed on the condition when battery voltage has fallen below a |
|
| preset value. If the input a.c. power cannot be restored, you should |
|
| shut down your loads. |
|
|
|