Liebert 130 kVA user manual Battery Connection, Emergency Stop, Back Feed Protection

Page 41

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

To Battery

+

 

Sensor

3

 

 

Temperature

2

 

 

(Optional)

1

 

 

 

 

X3

 

 

 

X4

 

 

 

X5

 

 

 

X6

 

 

 

X7

 

V<

 

X8

 

 

 

X9

+

BATTERY

X2

X10

 

CIRCUIT

 

1 2 3 4 5

 

BREAKER

X1

UPS CABINET

 

X3

Battery C.B.

 

1

 

2

Controller

 

3

 

 

4

 

 

5

 

 

6

 

 

7

 

 

8

 

 

9

 

+

10

 

11

 

 

12

 

Fig 3-3: Battery Connection

3.2.3Emergency Stop

If an external Emergency Stop facility is required it is connected to terminals 5 & 6 of the Auxiliary Terminal Block (X4) and connect the ‘normally closed’ remote stop switch between these two terminals using shielded cable. If this facility is not used then terminals 5 & 6 must be linked-out as shown in Figure 3-3.

Note: The Emergency Stop action within the UPS shuts down the rectifier, inverter and static bypass and trips the battery circuit breaker. It does not however internally disconnect the input mains supply. If required, this additional action can be facilitated by feeding the UPS input via a circuit breaker which can be tripped by a second contact of the Emergency Stop switch.

Note: Terminals 11 and 12 of the Auxiliary Terminal Block (X4) are connected to a normally closed contact of the UPS Display Panel Emergency Stop button and go open circuit when the button is pressed. This output can be used as part of a wider Emergency Stop system to initiate an external action (such as tripping an external supply breaker)

3.2.4Back Feed Protection

Using an auxiliary terminal (pins 9-10 of connector X4) the UPS provides a normally open contact to be used for opening of an external circuit protection device, to protect the operator against back feed of energy resulting from a short-circuit fault of the Bypass line SCRs. This auxiliary contact can be used, for example, in series with an external low voltage source, in order to supply the trip coil of an automatic circuit breaking device, located upstream of the UPS Bypass mains input. In the vent of energy being backfeed the auxiliary circuit will activate closing the normally open contact and as a result opening of the external circuit-breaking device; the UPS is disconnected from the Bypass mains supply. The electrical characteristics of the auxiliary contact are 50V (a.c. or d.c.) @ 1 Amp.

21

Image 41
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Introduction Single Module block diagramDesign Concept Hipulse Module DesignBypass Supplies UPS Power switches configurationOff-Battery Return of power mainsUPS Module fault Normal OperationOverload Maintenance BypassBattery circuit breaker UPS Power Switch ConfigurationBattery temperature compensation System ExpansionHipulse Single Phase ‘1+N’ UPS System Installation Procedure UPS location Battery locationEnvironmental considerations Mechanical Considerations Preliminary Checks Installation DrawingsOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details System Configuration Power CablingBattery cables Module input cablesCable rating Safety earthGeneral Notes Cable ConnectionsSplit Bypass Protection against earth faults RCD devicesProtective devices Cabling procedure UPS BatteryParallel 1+N Input ConnectionsAuxiliary Connections Input-module Parallel ConnectionsCable connections for 130 kVA 1Ph UPS +VE -VEAuxiliary Terminal Block detail Battery ControlControl cables Description Auxiliary Terminal Block X3 and X4 at UPSBack Feed Protection Battery ConnectionEmergency Stop Hipulse Single Phase ‘1+N’ UPS System UPS Operator Control / Display Panel Operator Control and Display PanelSingle module operator control panel Inverter control switchOperator control panel Mimic indicationsOperator Panel and LCD Display Menu Control switchesBargraph Selection Output ParametersMenu Options EPO on UPS moduleOr. for Instanc e Map of screen display available to operatorLCD Display Panel Messages Initializing Window Default WindowInfo Window Main Menu WindowAlarm / Warning Messages Option Selection ModeOn Static Bypass General notes Power SwitchesShutdown Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Normal Operation Your load is now powered via the Static Bypass systemYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Changing the current Date and Time Language SelectionHipulse Single Phase ‘1+N’ UPS System Safety Battery InstallationUPS Batteries Battery population Temperature considerationsBattery Racks Battery protectionConnecting the Battery IntroductionBattery Supply To UPS Cabinet Battery circuit breaker Battery InstallationBattery Control and Power Connections Battery temperature Board LED Interpretation Display Panel InterpretationProcedure to carry out the reset see Operating Instructions Display Panel Messages Sr. No Display Message Alarm InterpretationBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System General + N SystemBattery 1+N System block diagram with Separate BatteriesInter-module control Installation procedureConnection of 1+N system parallel single bus cables Connection of EPO Push Button Operating Instruction System Start-up and shutdown procedures Separate BatteriesDefault window Hipulse Single Phase ‘1+N’ UPS System Complete system shutdown Display Panel message interpretation in 1+N SystemUPS Environmental UPS Mechanical CharacteristicsConformity and Standard C T I F I E R I N P U T M a I N S UPS Electrical CharacteristicsRated Power KVA 130 UPS Electrical Characteristics DC Intermediate CircuitV E R T E R O U T P U T UPS Electrical Characteristics Inverter OutputProtection, bypass line UPS Electrical Characteristics Bypass Input MainsHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System RAM Connections Remote Alarm Monitor220/240V AC 50 Hz UPSProtection TerminationIndication & Metering Bypass Isolation Cubicle