User Manual
Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
| >INVERTER OFF | < | |
| BYPASS |
| ON |
| RECTIFIER |
| ON |
| RECTIFIER | MAN | |
|
|
|
|
|
|
|
|
| −ROTATE | START | ↵ |
|
| EXIT | ESC |
| INVERTER |
| ON |
|
|
|
|
|
|
|
|
The OFF selection will be highlighted, using the UP arrow key, rotate between the selections offered (in this case it will be ON or OFF) select ON. Press the ENTER key to execute your order.
After approximately 20 seconds, the Module Mimic will change so that the Load on Inverter (5) will light steady green and the Load on Bypass (6) will extinguish.
6a. Return the Display window to normal by repeatedly pressing ESCAPE key back through the various windows until the default screen is displayed.
The UPS is operating normally with its
Inverter supplying the load.
ECOMODE:
5b. Ensure BYPASS is selected by the cursor and press the ENTER key:
The OFF selection will be highlighted, using the UP arrow key, rotate between the selection offered (in this case it will be On or OFF) Select ON. Press the ENTER key to execute your order.
The Module Mimic LED’s will change: Load on Mains (6) will come on and Load on Inverter (5) will go out.
6b. Return the Display window to normal by repeatedly pressing ESCAPE key back through the various windows until the default screen is displayed.
The UPS is operating in ECOMODE with
Bypass Mains supplying the load.