Liebert 130 kVA user manual Environmental considerations, UPS location, Battery location

Page 28

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

2.2Environmental considerations

2.2.1UPS location

The UPS module should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Chapter 9 - Specifications).

All models in the ‘Hipulse’ UPS range are cooled with the aid of internal fans. Cooling air enters the module through ventilation grills located at various parts of the cabinet and exhausted through grills located on the back of UPS. When the cabinet is located on a raised floor, and bottom cable entry is used, additional cooling air also enters the UPS via the floor void. If necessary, a system of extractor fans should be installed to aid cooling air-flow, and a suitable air filtration system used where the UPS is to operate in a dirty environment.

Note 1: When batteries are cabinet-mounted adjacent to the UPS module, it is the battery which dictates the designed maximum ambient temperature, not the UPS.

Note 2: Power losses from the System which may be used in an air conditioning system are intended for operation using the Inverter, as in the ECOMODE configuration they would be undersized.

2.2.2Battery location

Temperature is a major factor in determining the battery life and capacity. Battery manufacturers quote figures for an operating temperature of 20oC. Operating above this temperature will reduce the battery life, operation below this temperature will reduce the battery capacity. On a normal installation the battery temperature is maintained between 15oC and 25oC. Batteries should be mounted in an environment where the temperature is consistent and even over the whole battery. Keep batteries away from main heat sources or main air inlets etc.

The batteries can be mounted in purpose-built battery cabinet, which is positioned adjacent to the UPS module. Pedestals are required for the battery cabinets when they are located on raised floors, in the same way as for the UPS cabinets. If the batteries are rack-mounted, or otherwise located remote to the main UPS cabinet, a battery circuit breaker must be mounted as close as possible to the batteries themselves, and connected using the most direct route possible. A customized remote battery circuit breaker box, containing the circuit breaker and its necessary control board, is also available as a standard option.

8

Image 28
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Single Module block diagram IntroductionDesign Concept Hipulse Module DesignUPS Power switches configuration Bypass SuppliesReturn of power mains Off-BatteryUPS Module fault Normal OperationMaintenance Bypass OverloadUPS Power Switch Configuration Battery circuit breakerBattery temperature compensation System ExpansionHipulse Single Phase ‘1+N’ UPS System Installation Procedure Environmental considerations Battery locationUPS location Mechanical Considerations Installation Drawings Preliminary ChecksOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Power Cabling System ConfigurationBattery cables Module input cablesSafety earth Cable ratingGeneral Notes Cable ConnectionsProtective devices Protection against earth faults RCD devicesSplit Bypass UPS Battery Cabling procedureParallel 1+N Input ConnectionsInput-module Parallel Connections Auxiliary Connections+VE -VE Cable connections for 130 kVA 1Ph UPSControl cables Battery ControlAuxiliary Terminal Block detail Auxiliary Terminal Block X3 and X4 at UPS DescriptionEmergency Stop Battery ConnectionBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System Operator Control and Display Panel UPS Operator Control / Display PanelInverter control switch Single module operator control panelOperator control panel Mimic indicationsMenu Control switches Operator Panel and LCD DisplayOutput Parameters Bargraph SelectionEPO on UPS module Menu OptionsMap of screen display available to operator Or. for Instanc eDefault Window LCD Display Panel Messages Initializing WindowInfo Window Main Menu WindowOption Selection Mode Alarm / Warning MessagesShutdown General notes Power SwitchesOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Your load is now powered via the Static Bypass system Normal OperationYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Language Selection Changing the current Date and TimeHipulse Single Phase ‘1+N’ UPS System Battery Installation SafetyUPS Batteries Temperature considerations Battery populationBattery protection Battery RacksConnecting the Battery IntroductionBattery Supply To UPS Cabinet Battery Installation Battery circuit breakerBattery Control and Power Connections Battery temperature Board Display Panel Interpretation LED InterpretationProcedure to carry out the reset see Operating Instructions Sr. No Display Message Alarm Interpretation Display Panel MessagesBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System + N System General1+N System block diagram with Separate Batteries BatteryConnection of 1+N system parallel single bus cables Installation procedureInter-module control Connection of EPO Push Button System Start-up and shutdown procedures Separate Batteries Operating InstructionDefault window Hipulse Single Phase ‘1+N’ UPS System Display Panel message interpretation in 1+N System Complete system shutdownConformity and Standard UPS Mechanical CharacteristicsUPS Environmental UPS Electrical Characteristics C T I F I E R I N P U T M a I N SUPS Electrical Characteristics DC Intermediate Circuit Rated Power KVA 130UPS Electrical Characteristics Inverter Output V E R T E R O U T P U TUPS Electrical Characteristics Bypass Input Mains Protection, bypass lineHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Remote Alarm Monitor RAM ConnectionsUPS 220/240V AC 50 HzIndication & Metering TerminationProtection Bypass Isolation Cubicle