Liebert 130 kVA user manual Display Panel Interpretation, LED Interpretation

Page 75

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

CHAPTER 7

Display Panel Interpretation

7.1LED Interpretation:

The LED item number refers to details shown in the figure 7.1 below.

6

1

 

 

 

2

 

 

 

3

 

INV

 

 

 

 

4

5

7

8

 

 

DISPLAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

%

 

 

 

 

 

MENU

 

 

 

 

 

 

 

 

ESC

 

 

ENTER

 

 

 

 

 

 

 

9

10

11

12

13

14

15

16

17

18

19

 

 

 

Fig 7-1: Single module operator control panel

 

 

 

LED N0.

NORMAL

INTERPRETATION – ACTION

 

STATE

 

 

1.

ON

If this green led is OFF, it signifies a problem with the Bypass input a.c.

 

 

Check the following –

 

 

1.

Bypass input power switch Q2 is closed.

 

 

2.

Input Supply voltage is within 10% of nominal

 

 

3.

Power supply fuses are OK – on the a.c. Power supply board will extinguish if either fuse is

 

 

 

ruptured.

 

 

If the above checks prove unsatisfactory then seek qualified assistance.

2.

ON

If this led is OFF, a problem exists in the Input power supply or in a part of the rectifier. An alarm message

 

 

is visible at the display.

 

 

Check the following –

 

 

1.

The rectifier input isolator (Q1) is closed.

 

 

2.

The input voltage is within the limits of normal operation.

 

 

3.

The phase sequence of the mains input is correct.

 

 

4.

Verify that condition leading to an emergency stop has not happened, in which case a Reset

 

 

 

must be carried out.

 

 

If these checks do not give a positive result, request qualified assistance.

3.

OFF

If this yellow led is ON it signifies that the battery is not available. This could be due to the battery circuit

 

 

breaker being open or that the d.c. busbar voltage is below the figures stated in the item(2) specified

 

 

above.

 

 

 

The battery circuit breaker will open automatically if the d.c. voltage falls below these levels.

 

 

Check the following –

 

 

1.

Check that the conditions for led(2) are satisfied.

 

 

2.

DC busbar voltage – if not above 320V, then carry out checks as for led(2) – mains rectifier

 

 

 

failure above. If d.c. busbar voltage is above 320V but you are unable to close the battery

 

 

 

circuit breaker then seek qualified assistance.

 

 

3.

Battery circuit breaker is closed.

 

 

If the above checks prove unsatisfactory, then seek qualified assistance.

 

 

 

 

4.

ON

If this green led is OFF, it signifies that the inverter is not producing its correct output voltage.

Check the following –

55

Image 75
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Hipulse Module Design Single Module block diagramIntroduction Design ConceptBypass Supplies UPS Power switches configurationNormal Operation Return of power mainsOff-Battery UPS Module faultOverload Maintenance BypassSystem Expansion UPS Power Switch ConfigurationBattery circuit breaker Battery temperature compensationHipulse Single Phase ‘1+N’ UPS System Installation Procedure Battery location Environmental considerationsUPS location Mechanical Considerations Preliminary Checks Installation DrawingsOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Module input cables Power CablingSystem Configuration Battery cablesCable Connections Safety earthCable rating General NotesProtection against earth faults RCD devices Protective devicesSplit Bypass Input Connections UPS BatteryCabling procedure Parallel 1+NAuxiliary Connections Input-module Parallel ConnectionsCable connections for 130 kVA 1Ph UPS +VE -VEBattery Control Control cablesAuxiliary Terminal Block detail Description Auxiliary Terminal Block X3 and X4 at UPSBattery Connection Emergency StopBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System UPS Operator Control / Display Panel Operator Control and Display PanelMimic indications Inverter control switchSingle module operator control panel Operator control panelOperator Panel and LCD Display Menu Control switchesBargraph Selection Output ParametersMenu Options EPO on UPS moduleOr. for Instanc e Map of screen display available to operatorMain Menu Window Default WindowLCD Display Panel Messages Initializing Window Info WindowAlarm / Warning Messages Option Selection ModeGeneral notes Power Switches ShutdownOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Normal Operation Your load is now powered via the Static Bypass systemYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Changing the current Date and Time Language SelectionHipulse Single Phase ‘1+N’ UPS System Safety Battery InstallationUPS Batteries Battery population Temperature considerationsIntroduction Battery protectionBattery Racks Connecting the BatteryBattery Supply To UPS Cabinet Battery circuit breaker Battery InstallationBattery Control and Power Connections Battery temperature Board LED Interpretation Display Panel InterpretationProcedure to carry out the reset see Operating Instructions Display Panel Messages Sr. No Display Message Alarm InterpretationBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System General + N SystemBattery 1+N System block diagram with Separate BatteriesInstallation procedure Connection of 1+N system parallel single bus cablesInter-module control Connection of EPO Push Button Operating Instruction System Start-up and shutdown procedures Separate BatteriesDefault window Hipulse Single Phase ‘1+N’ UPS System Complete system shutdown Display Panel message interpretation in 1+N SystemUPS Mechanical Characteristics Conformity and StandardUPS Environmental C T I F I E R I N P U T M a I N S UPS Electrical CharacteristicsRated Power KVA 130 UPS Electrical Characteristics DC Intermediate CircuitV E R T E R O U T P U T UPS Electrical Characteristics Inverter OutputProtection, bypass line UPS Electrical Characteristics Bypass Input MainsHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System RAM Connections Remote Alarm Monitor220/240V AC 50 Hz UPSTermination Indication & MeteringProtection Bypass Isolation Cubicle