User Manual
Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
CHAPTER 7
Display Panel Interpretation
7.1LED Interpretation:
The LED item number refers to details shown in the figure 7.1 below.
6
1 |
|
|
|
2 |
|
|
|
3 |
| INV |
|
|
|
| |
4 | 5 | 7 | 8 |
|
| DISPLAY |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| % |
|
|
|
|
| MENU |
|
|
|
|
|
|
|
|
ESC |
|
| ENTER |
|
|
|
|
|
|
|
9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 |
|
|
| Fig |
|
|
| |
LED N0. | NORMAL | INTERPRETATION – ACTION | |
| STATE |
|
|
1. | ON | If this green led is OFF, it signifies a problem with the Bypass input a.c. | |
|
| Check the following – | |
|
| 1. | Bypass input power switch Q2 is closed. |
|
| 2. | Input Supply voltage is within 10% of nominal |
|
| 3. | Power supply fuses are OK – on the a.c. Power supply board will extinguish if either fuse is |
|
|
| ruptured. |
|
| If the above checks prove unsatisfactory then seek qualified assistance. | |
2. | ON | If this led is OFF, a problem exists in the Input power supply or in a part of the rectifier. An alarm message | |
|
| is visible at the display. | |
|
| Check the following – | |
|
| 1. | The rectifier input isolator (Q1) is closed. |
|
| 2. | The input voltage is within the limits of normal operation. |
|
| 3. | The phase sequence of the mains input is correct. |
|
| 4. | Verify that condition leading to an emergency stop has not happened, in which case a Reset |
|
|
| must be carried out. |
|
| If these checks do not give a positive result, request qualified assistance. | |
3. | OFF | If this yellow led is ON it signifies that the battery is not available. This could be due to the battery circuit | |
|
| breaker being open or that the d.c. busbar voltage is below the figures stated in the item(2) specified | |
|
| above. |
|
|
| The battery circuit breaker will open automatically if the d.c. voltage falls below these levels. | |
|
| Check the following – | |
|
| 1. | Check that the conditions for led(2) are satisfied. |
|
| 2. | DC busbar voltage – if not above 320V, then carry out checks as for led(2) – mains rectifier |
|
|
| failure above. If d.c. busbar voltage is above 320V but you are unable to close the battery |
|
|
| circuit breaker then seek qualified assistance. |
|
| 3. | Battery circuit breaker is closed. |
|
| If the above checks prove unsatisfactory, then seek qualified assistance. | |
|
|
|
|
4.
ON
If this green led is OFF, it signifies that the inverter is not producing its correct output voltage.
Check the following –
55