Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V | |
22. | BATTERY ON LOAD | This is a status warning that the battery is discharging. It normally |
|
| accompanies a [BYP: ABSENT] or [RECT: OFF] message. |
23. | AUTONOMY XXXX min | The micro monitors the battery percentage capacity while on charge |
|
| and the battery time remaining while on discharge. It calculates the |
|
| time remaining as function of the discharge current against the |
|
| programmed |
|
| time remaining as the load is change. |
|
|
|
24. | BATTERY UNDER TEST | This message informs the operator that the system is carrying out a |
|
| periodic battery test. |
25. | BOOST TIME EXPIRED | This message is only applicable to systems which include the boost |
|
| charge option, boost time charge elapsed set value, battery should |
|
| be controlled by service personnel. |
26. | LOAD ON BYPASS | This is a status warning that the load is being powered through the |
|
| static bypass line and is unprotected from mains supply |
|
| aberrations. |
|
| This action is either selected by the operator or a fault condition, |
|
| check for other fault messages. |
|
|
|
27. | RECT: OFF | This is a status message confirming that the rectifier has been |
| RECT: OFF VIA DISPLAY | selected off by the operator from either the front panel display or an |
|
| external PC or by a switch on UPS microprocessor PCB. |
28. | BYP: OFF | This is a status message confirming that the bypass has been |
| BYP: OFF VIA DISPLAY | inhibited by the operator from either an external PC or by a switch |
|
| on UPS microprocessor PCB. |
29. | INV: OFF | This is a status message confirming that the inverter has been |
| INV: OFF VIA DISPLAY | selected off by the operator from either the front panel display or an |
|
| external PC or by a switch on UPS micro controller PCB. |
|
|
|
60