Liebert 130 kVA user manual Auxiliary Terminal Block X3 and X4 at UPS, Description

Page 40

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

3.2.2Auxiliary Terminal Block X3 and X4 at UPS

X3 terminal reference

Reference label

Description

 

 

 

2

Common

Temperature sensor common (0V)

 

 

 

3

T Batt.

Temperature sensor signal

 

 

 

4

Common

Common (0V)

 

 

 

5

Batt. Sw.

Battery circuit breaker trip control

 

 

 

6

Bat Trp

Battery circuit breaker trip control

 

 

 

Note: The auxiliary cables of the battery must be screened and double insulated. The screen is connected to the earth of the battery cabinet or supporting rack. Use multiple-core shielded cables with a section of 0.5 to 1mm2

Connect the cables with the Fast-on 6.3 x 0.8 mm terminals (female)

X4 terminal reference

Reference label

Description

 

 

 

1-2

Ext. OFF Inv

Remotely provides control for switching off the inverter.

Normally open contact.

 

 

 

 

Indication to be provided at the UPS to note the opening of an external

3-4

Ext. Sw. Out

module output isolator.

Normally closed contact.

 

 

 

 

If unused, leave the standard connectors in place.

 

 

Remotely provides control for switching off the UPS using a remote

5-6

Ext. EPO

emergency button.

Normally closed contact.

 

 

 

 

If unused, leave the standard connectors in place.

 

 

Indication to be provided at the UPS to note the opening of an external

7-8

Ext. BYP

maintenance bypass switch.

Normally closed contact.

 

 

 

 

If unused, leave the standard connectors in place.

9-10

Back Feed

Signal form the UPS to indicate a return flow of energy in the bypass mais.

Normally open contact.

 

 

 

 

Availability of a contact for switching off the UPS in the same way as the

11-12

Int. EPO

internal emergency off button.

 

 

Normally closed contact.

Note: All auxiliary cables of terminal block X4 must be double insulated.

The cross-sectional area of the auxiliary cables is from 0.5 to 1 mm2

Connect the cables with the Fast-on 6.3 x 0.8 mm terminals (female)

Maximum contact rating on auxiliary terminals: 50 Vdc @ 1 Amp.

20

Image 40
Contents Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Dear Customer Hipulse Single Phase ‘1+N’ UPS System Rev. No Revision details Hipulse Single Phase ‘1+N’ UPS System Registered Head Office Hipulse Single Phase ‘1+N’ UPS System East Zone Hipulse Single Phase ‘1+N’ UPS System Safety Procedure Hipulse Single Phase ‘1+N’ UPS System General Hipulse Single Phase ‘1+N’ UPS System General Introduction Hipulse Single Phase ‘1+N’ UPS System Operating Instructions Hipulse Single Phase ‘1+N’ UPS System Annexure Hipulse Single Phase ‘1+N’ UPS System Single Module block diagram IntroductionDesign Concept Hipulse Module DesignUPS Power switches configuration Bypass SuppliesReturn of power mains Off-BatteryUPS Module fault Normal OperationMaintenance Bypass OverloadUPS Power Switch Configuration Battery circuit breakerBattery temperature compensation System ExpansionHipulse Single Phase ‘1+N’ UPS System Installation Procedure Environmental considerations Battery locationUPS location Mechanical Considerations Installation Drawings Preliminary ChecksOverall General Arrangement for 130kVA Single Phase UPS Cable Entry Details Power Cabling System ConfigurationBattery cables Module input cablesSafety earth Cable ratingGeneral Notes Cable ConnectionsProtective devices Protection against earth faults RCD devicesSplit Bypass UPS Battery Cabling procedureParallel 1+N Input ConnectionsInput-module Parallel Connections Auxiliary Connections+VE -VE Cable connections for 130 kVA 1Ph UPSControl cables Battery ControlAuxiliary Terminal Block detail Auxiliary Terminal Block X3 and X4 at UPS DescriptionEmergency Stop Battery ConnectionBack Feed Protection Hipulse Single Phase ‘1+N’ UPS System Operator Control and Display Panel UPS Operator Control / Display PanelInverter control switch Single module operator control panelOperator control panel Mimic indicationsMenu Control switches Operator Panel and LCD DisplayOutput Parameters Bargraph SelectionEPO on UPS module Menu OptionsMap of screen display available to operator Or. for Instanc eDefault Window LCD Display Panel Messages Initializing WindowInfo Window Main Menu WindowOption Selection Mode Alarm / Warning MessagesShutdown General notes Power SwitchesOn Static Bypass Location of Power Isolators Ecomode the message Load on Bypass will not appear Battery C.B. Open Bypass Switch Open Ecomode Your load is now powered via the Static Bypass system Normal OperationYour load is now powered via the Static Bypass system Procedure for completely powering down the UPS UPS is now completely powered down Adding a single module to an existing system If YOU are not Sure What YOU are Doing Then do not do IT Ecomode INV OFF VIA Display Load on Bypass Setting the Battery Test Language Selection Changing the current Date and TimeHipulse Single Phase ‘1+N’ UPS System Battery Installation SafetyUPS Batteries Temperature considerations Battery populationBattery protection Battery RacksConnecting the Battery IntroductionBattery Supply To UPS Cabinet Battery Installation Battery circuit breakerBattery Control and Power Connections Battery temperature Board Display Panel Interpretation LED InterpretationProcedure to carry out the reset see Operating Instructions Sr. No Display Message Alarm Interpretation Display Panel MessagesBypass Switch Open BYP. Absent Battery Under Test BYP Xfer Count Block Hipulse Single Phase ‘1+N’ UPS System + N System General1+N System block diagram with Separate Batteries BatteryConnection of 1+N system parallel single bus cables Installation procedureInter-module control Connection of EPO Push Button System Start-up and shutdown procedures Separate Batteries Operating InstructionDefault window Hipulse Single Phase ‘1+N’ UPS System Display Panel message interpretation in 1+N System Complete system shutdownConformity and Standard UPS Mechanical CharacteristicsUPS Environmental UPS Electrical Characteristics C T I F I E R I N P U T M a I N SUPS Electrical Characteristics DC Intermediate Circuit Rated Power KVA 130UPS Electrical Characteristics Inverter Output V E R T E R O U T P U TUPS Electrical Characteristics Bypass Input Mains Protection, bypass lineHipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Hipulse Single Phase ‘1+N’ UPS System Remote Alarm Monitor RAM ConnectionsUPS 220/240V AC 50 HzIndication & Metering TerminationProtection Bypass Isolation Cubicle