User Manual
Hipulse - Single Phase ‘1+N’ UPS System | 130 kVA - 110V |
9.7UPS Electrical Characteristics (Bypass Input Mains)
|
| B Y P A S S I N P U T M A I N S |
|
|
|
Rated Power | kVA | 130 |
|
|
|
Rated mains voltage j | Vac | 380 - 400 - 415 |
|
| |
|
|
|
Supply |
| Three phase with neutral |
|
|
|
Rated Current: | A | 1182 |
110 Vac |
|
|
|
|
|
Bypass voltage tolerance k | % | ± 10 |
|
|
|
Delay time to recognize bypass | sec | 10 |
voltage returned to window |
|
|
Inverter output voltage window | % | ± 10 |
|
|
|
Frequency l | Hz | 50 or 60 |
|
|
|
Input frequency tolerance m | % | ± 2 |
|
| |
|
|
|
Maximum frequency slew rate | Hz |
|
| /sec | 0.1 |
|
|
|
Current rating of neutral cable |
| 1.5 x In |
|
| |
|
|
|
Protection, bypass line |
| To avoid series fuses, the bypass line should be protected using an |
|
| external device should be sized to discriminate with the load |
|
| protection. |
Overload | % | 150% for 60 sec |
|
| 125% for 10 min |
|
| 110% for 1 hr |
Note:
j= Factory set 400V – 380V or 415V set changing taps on auxiliary supply transformer and with software setting k = Other values
l = Factory set at 50Hz ; 60Hz with software setting. m = Other values
75